U-MATCH AIR CONDITIONERS MAINTENANCE
96
Malfunction display: E4 Compressor Exhaust High Temperature Protection
Compressor Exhaust High
Temperature Protection
Check if the capacity output of the outdoor
unit meets with the capacity requirement of
the indoor unit?
check if the liquid bypass parts are in good
conditions, for examples, if the solenoid
valve works properly or the capillary is
clogged?
check if the liquid bypass plug is connected
when the air exhaust temperature of the
compressor exceeds 115
ć
?
Check if the air exhaust temperature has
reached 130
ć˛
Yes
Yes
Yes
Yes
Check if the resistance value of the
sensor is correct?
Replace the main board of the
outdoor unit
Repair if system tube is
leaking and add refrigerant of
the same quality
refer to capacity code
Replace the liquid bypass
parts
No
No
No
No
replace the corresponding
discharge temperature sensor
No
Yes
Summary of Contents for u-match on/off
Page 1: ......
Page 4: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 1 PRODUCT...
Page 24: ...U MATCH AIR CONDITIONERS PRODUCT 21 5 PIPING DIAGRAM...
Page 25: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 22 CONTROL...
Page 26: ...U MATCH AIR CONDITIONERS CONTROL 23 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...
Page 27: ...U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Page 45: ...U MATCH AIR CONDITIONERS CONTROL 42 5 2 4 Dimensions...
Page 48: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 45 INSTALLATION...
Page 91: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 88 MAINTENANCE...
Page 101: ...U MATCH AIR CONDITIONERS MAINTENANCE 98 Malfunction display E6 Communications Failure...
Page 115: ...U MATCH AIR CONDITIONERS MAINTENANCE 112...
Page 163: ......