![INVENTOR u-match on/off Service Manual Download Page 78](http://html1.mh-extra.com/html/inventor/u-match-on-off/u-match-on-off_service-manual_2084115078.webp)
U-MATCH AIR CONDITIONERS INSTALLATION
75
Curvature of piping shall not be too small, or otherwise piping may be broken. So installation
personnel should use a pipe bender to bend pipes.
Upward or longitudinal welding joint method is usually applied to the welding of pipelines.
The welding method that mouth of pipe is downward (face-down welding) should be avoided
as far as possible, because such method is prone to welding defects and even would cause
leakage, as shown in Figure 3-1-3.
Figure 3-1-3
Uninsulated connecting pipes and connectors should be packed with sponge and tied with
plastic adhesive tapes.
2
˅
Vacuum-pumping and leak detection
Dismantle the bonnet of refrigerant valve and air valve.
Align with the center of piping and adequately tighten nuts of connecting pipes by hand
Tighten the nuts with a spanner.
Remove the one way valve cap of air valve.
Unscrew the spool of refrigerant valve for 1/4 turn with a socket head wrench, and at the
same time push up the spool of air valve with a screwdriver to let air give off.
Air exhaust continues for 15 seconds until coolant gas appears, immediately shut off one way
valve and tighten the valve cap.
Totally open the spool of refrigerant valve and air value (as shown in Figure 3-1-4)
Figure 3-1-4
Summary of Contents for u-match on/off
Page 1: ......
Page 4: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 1 PRODUCT...
Page 24: ...U MATCH AIR CONDITIONERS PRODUCT 21 5 PIPING DIAGRAM...
Page 25: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 22 CONTROL...
Page 26: ...U MATCH AIR CONDITIONERS CONTROL 23 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...
Page 27: ...U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Page 45: ...U MATCH AIR CONDITIONERS CONTROL 42 5 2 4 Dimensions...
Page 48: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 45 INSTALLATION...
Page 91: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 88 MAINTENANCE...
Page 101: ...U MATCH AIR CONDITIONERS MAINTENANCE 98 Malfunction display E6 Communications Failure...
Page 115: ...U MATCH AIR CONDITIONERS MAINTENANCE 112...
Page 163: ......