45
TROUBLESHOOTING AND DISPOSAL
sMove controller
•
Installation and operation manual
11
Troubleshooting and disposal
Troubleshooting
If your ventilation units or controllers are not functioning properly, consult the following
troubleshooting table. If the fault persists, contact your supplier, distributor or the technical
service department at inVENTer GmbH (see chapter 11 – service)
Malfunction
Possible cause
Remedy
Wrong controller
function when inter-
face is connected
Upper jumper is
incorrectly/not connected
Check position of the jumper on the back
of the operating unit:
• attached: OFF (NC contact - pressure
monitor)
• not attached: Continuous ventilation
mode, level 3 (NO contact (Hygrostat,
CO
2
sensor, VOC sensor)
Fans without
function
Pressure monitor connec-
ted as an closer contact
(NO) (e. g. exchange of
operating unit)
Changeover of the pressure sensor as
normally closed contact (changeover
contact) or exchange for a pressure
sensor with normally closed contact, if
necessary.
Controller does not
function.
Operating unit is incorrect-
ly/not connected.
Check wiring.
No electrical contact.
Check cables. Ensure cables are stripped
sufficiently (approx. 8.5 mm).
Indicator lights do
not light up.
Faulty controller.
Replace controller.
There is no power.
Check power supply.
Slide control
defective.
Replace controller.
Disassembly and disposal
Dissassemble the controller in the opposite sequence to the assembly sequence. You
can subsequently dispose of your old device. The products described in these installa-
tion and operating instructions contain valuable materials which can be recovered and
recycled.
The separation of waste materials into different varieties facilitates recovery of
the recyclable materials. Contact an electronic appliance disposal company to arrange
environmentally friendly recycling and disposal of your old system.
They will dispose of the product in compliance with the applicable national regulations.
Product
Material
Disposal
Operating unit casing
ABS
Plastic recycling
Operating unit glass plate
Acrylic glass
Residual waste
PCB/switching PSU
Electronics
Collection point for electrical
appliances