29
INSTALLATION AND ASSEMBLY
sMove controller
•
Installation and operation manual
Connecting the flush mounted switching PSU
DANGER
Exposed electrical components.
Electric shock and injury due to live components (230V, 50Hz)!
•
Before working on electrical installations, disconnect all affected equipment from the power supply.
• Observe the requirements for protection class II when laying the power supply cable.
Do not lay live cables.
• Lay the Fan-BUS and power cables separately.
•
Connection of the power supply cable must only be performed by qualified and trained
personnel.
Isolating terminal, filler for installing the box, cover for the box (e.g. cover with switch
design)
Requirements:
The cables are laid. The power supply is disconnected.
►
Break out a cable entry for the power supply cable
at the bottom of the flush-mounted box.
►
Break out a cable entry
• for the fan-BUS connection cable
•
for the connection cable for the optional
sensor
at the opening in the flush-mounted box.
►
Insert the prepared flush-mounted box into the
wall opening.
Ö
Das Unterputz-Schaltnetzteil ist angeschlossen.
►
Lay the power supply cable, 230 V AC, through the
cable entry on the base of the flush-mounted box.
►
Insulate the wire safety contact on the power
supply cable with a terminal.
►
Feed the
• fan-BUS connection cable
• connection cable for the optional sensor
into the flush-mounted box
.
►
Fill the space between the interior wall and the
box with a suitable filler.
►
Connect the
PSU's input cable
(blue/brown) via
the lustre terminal:
• Connect the phase conductor with
cable L (brown).
• Connect the neutral conductor with
cable N (blue).
►
Slide the connected PSU into the box.
Ensure that
the PSU's output cable protrudes into
the interior space.