OPERATION

sMove controller 

 Installation and operation manual

Operation

The sMove controller consists of a base plate for mounting on the inner wall and an operating 

unit. The operating unit contains the electronics of the sMove as well as the control panel 

(acrylic glass cover). The control panel serves as input and display surface for the user.

Control panel

The control panel is located on the front of the control unit and also serves as a display surface. 

It is composed of capacitive buttons and various indicator lights. It is operated by touching the 

various buttons (marked in grey in figure 2).

Figure 13: Vorderansicht Bedieneinheit Regler sMove

1  Marker for output levels 1 – 4

2  Continuous ventilation mode 

   (blue) indicator light / 

   filter change indicator (blue flashing)

3  Operating mode button

4  Heat recovery mode 

   (orange) indicator light / 

   filter change indicator (orange flashing)

Pause/Off indicator light

Pause/Off button

7  Output level indicator lights

8  Slide control

1

2
3
4

5

6

7

8

Slide control:

Briefly pressing the fan symbol allows you to select one of the four specific output levels. 

Touching the slide control for approx. one second lets you continuously adjust the output level by 

moving it. The position of the illuminated display on the left side of the slide control indicates the 

currently set output level. 

 

Mode button: 

Pressing repeatedly lets you switch between the heat recovery and continuous ventilation 

modes. The indicator lights to the left of the Mode button displays the currently set mode.

The output level of the ventilation unit can be adjusted in all operating modes.

Output level

Symbol

Flow rate [%]

1

25

2

35

3

50

4

100

Summary of Contents for sMove S4 Long

Page 1: ...sMove s4 s8 Installation and operating instructions ...

Page 2: ...docu mentation has been checked for compliance with the described hard ware and software Nevertheless deviations may still occur therefore no guarantee of compliance can be provided This documentation de scribes the functionality of the standard scope The documentation does not purport to cover all details on all types of the product and cannot cover every conceivable scenario for operation cleani...

Page 3: ... 5 1 Check the scope of supply 21 5 2 Fitting the wall openings 22 5 3 Laying the cables 23 5 4 sMove s4 s8 controller Installation with cabinted mounted PSU 24 5 5 sMove s4 controller Installation with flush mounted switching PSU 26 5 6 sMove s8 controller Installation with flush mounted switching PSU 27 5 7 Installing the operating unit 30 6 Operation 33 6 1 First activation 35 6 2 Setting heat ...

Page 4: ...zards and or damage Other symbols and notices used in this documentation In addition to the safety instructions the following symbols are used A TIP symbol indicates practical and useful tips for handling the sMove controller A tool symbol before an installation sequence lists any additional tools and materials required for the described task Action required this requires the user to perform a spe...

Page 5: ...f protection class II Do not lay live cables The mains power supply must correspond to the specifications on the device information plate Before working on electrical installations disconnect all af fected equipment from the power supply Connect all controllers for one ventilation systemon the same circuit breaker CAUTION Operation and or maintenance of the ventilation unit and its controllers mus...

Page 6: ...display surface due to integrated illuminated displays The sMove can be used either as a base module or with additional sensors connected When used as a basic control unit it is possible to select the operating mode of the ventilation unit and to set the air volume flow either continuously or in 4 predefined steps The connected ventilation unitss can be controlled in the following modes Heat recov...

Page 7: ...ur when in pause mode Subsequently the ventilation device continues to work in heat recovery mode at the lowest output level The use of the flat version is recommended in areas where it is desirable not to turn off the ventilation system in order to maintain humidity levels Standard version in addition to pause mode the standard version provides the option to switch off the ventilation device comp...

Page 8: ...slide control indicates the currently set output level sMove controller with connected interface advanced features The external interface is a bi functional port on the back of the operating unit It enables the connection of a sensor with a potential free switching contact NO NC or the use of an analogue input to integrate the ventilation system into an existing home automation system Connecting t...

Page 9: ...ch all ventilation devices connected to the controller to the OFF mode Switch all ventilation devices connected to the controller to the originally set mode CO2 sensor Closer contact NO Switch all ventilation devices connected to the controller to ventilation mode output level 3 Switch all ventilation devices connected to the originally set mode VOC sensor Hygrostat B Interface as analogue input I...

Page 10: ...output level Mode button Pressing repeqtedly lets you switch between the heat recovery and continuous ventilation modes The indicator lights to the left of the Mode button displays the currently set mode Pause Off button A brief press of the controller allows you to switch to the pause function for a chosen time In the standard version pressing the button for 5 seconds allows you to completely swi...

Page 11: ...eed Only use the following cable cross sections Fan BUS Min 0 75 mm Operating voltage cable 0 75 1 5 mm Power supply cable 1 5 mm TIP Connect the reversible fans in a star shaped configuration and ensure sufficient clearance for the cables Observe the maximum distances maximum cable lengths Schematic sketches Connection options for ventilation units to the sMove Cabinet mounted power supply unit F...

Page 12: ...um distance between controller and the last connected ventilation unit sMove s4 with 4 x iV Smart iV14 Zero iV Light iV Compact Max 15 m sMove s4 with 2 x iV Smart iV14 Zero iV Light iV Compact Max 25 m sMove s4 with 2 x iV25 iV Twin Max 15 m Connection example for controller sMove s4 with cabinet mounted PSU Figure 3 Connection example for controller sMove s4 with cabinet mounted PSU and distribu...

Page 13: ...gue input 2 Switching contact 2 Sk2 Analogue input Figure 4 Connection example for controller sMove s4 with flush mounted PSU and distribution 24 V DC GND Lü1 Ub Lü2 III IV V III IV V III IV V III IV V L PE N AC DC I I II II III IV V 1 2 III IV V Steckbrücke Jumper 2 1 1 Plug in connection 2 Reversible fan 3 Mounting box 4 Connecting terminal block 5 Rear side of operating unit 6 Jumper for extern...

Page 14: ... between controller and the last connected ventilation unit sMove s8 with 8 x iV Smart iV14 Zero iV Light iV Compact Max 10 m sMove s8 with 4 x iV Smart iV14 Zero iV Light iV Compact Max 20 m sMove s8 with 4 x iV25 iV Twin Max 10 m Connection example for controller sMove s8 with cabinet mounted PSU Figure 5 Connection example for controller sMove s8 with cabinet mounted PSU and distribution Fan BU...

Page 15: ...ace potential free switching contact or analogue control cable 0 10 V 1 Switching contact 1 Sk1 Analogue input 2 Switching contact 2 Sk2 Analogue input 1 Reversible fan 2 Plug in connection 3 Mounting box for operating unit 4 Rear side of operating unit 5 Jumper for external interface 6 Jumper for service settings 7 Terminal 5 pole Fan BUS Controller operating voltage 8 Terminal 2 pole External in...

Page 16: ... cable for flush mounted PSU L AC L Phase conductor N AC N Neutral conductor Controler operating voltage Output cable for flush mounted PSU 24 V Controller operating voltage GND Rear side of sMove controller operating unit Terminal 5 pole Controller operating voltage I 24 V Controller operating voltage II GND Fan BUS connection III Lü1 Ground 1 IV Ub Fan operating voltage V Lü2 Ground 2 Terminal 2...

Page 17: ... settings and must be left as delivered to ensure correct functioning of the controller If a pressure monitor with normally open contact is connected e g if the sMove controller is exch anged it must be configured as a normally closed contact switch with changeover contact or if this is not possible it must be replaced by a pressure monitor with normally closed contact It is not possible to connec...

Page 18: ...the ventilation unit The connection terminal for the fan BUS can connect strands up to 1 5 mm 4 2 Dimensions TIP ideally install the flush mounted box or flush mounted plasterboard box for the operating unit at the same height as the existing light switches sMove s4 s8 incl control panel PSU 1 flush mounted plasterboard box min depth 66 mm sMove s4 incl flush mounted PSU 1 flush mounted box 1 wall...

Page 19: ...mounted switching PSU NT17 s4 32 5 54 4 3 Dimensioned drawings sMove controller 1 Receiver for locking lever 2 Receiver 4 x for base plate guides 1 Guides 4 x for attaching the operating unit 2 Installation marking TOP 3 Box fixing points 4 x 4 Locking lever for the operating unit 73 70 70 73 2 4 60 3 1 1 86 86 24 14 2 1 Figure 8 Dimensioned drawing front view base plate for sMove controller Figur...

Page 20: ...66 80 66 25 Ø 80 95 66 4 1 3 Ø 60 4 2 3 Figure 10 Flush mounted box 60x92 60x66 1 Flush mounted box 60x66 2 Putzausgleichsring preassembled box 60x92 only 3 Base plate fixing points 2 x 4 Wall opening 61 Ø 68 60 Ø 75 2 1 2 1 Fixing screw for plasterboard wall box 2 Fixing screw for operating unit 2x Mounting boxes Figure 11 Plasterboard wall box 61x68 Figure 12 Plasterboard wall box 70x87 ...

Page 21: ...nd power cables separately The installation and connection must only be performed by qualified and trained personnel 5 1 Check the scope of supply Check the delivery for completeness and transport damage upon receipt using the delivery note Report missing items immediately and at the latest within 14 days to your supplier distrib utor or factory representative 1 only ordered PSU selection 1 sMove ...

Page 22: ...sonry must be dry and in a load bearing condi tion The plasterboard wall must be finished No lintels in the location of the planned drill holes Ø Ø 2 x Create a hole for the box in the interior wall Observe the maximum cable lengths 4 Ø sMove s4 s8 with cabinet mounted PSU flush mounted box Ø 82 mm depth 66 mm plasterboard box Ø 68 mm depth 66 mm sMove s4 with flush mounted PSU flush mounted box Ø...

Page 23: ...equirement The wall openings are created sMove s4 with flush mounted PSU sMove s4 s8 with cabinet mounted PSU Lay the power supply cable mains 230 V AC to the wall opening for the connection to the flush mounted PSU Lay the fan cables 3 wire between ventilation unit and wall opening for the operating unit s connection Ö Ö You have laid the cables Lay the operating voltage cable 2 wire to the wall ...

Page 24: ... power supply requires 1 5 TE space sMove s8 The switching power supply requires 4 5 TE space Connect the PSU see section 4 Electrical connections Terminal assignments Attach the phase conductor to terminal L Attach the neutral conductor to terminal N Attach the red conductor to the terminal Attach the blue conductor to the terminal Ö Ö The switching PSU is connected L N 24 V DC 230 V AC 1 2 3 4 L...

Page 25: ...able Requirements The wall openings are created The cables are laid Ö Ö The wall box is mounted Proceed with installation of the operating unit see section 5 7 Installing the operating unit Break out a cable entry for each pair of fans for the operating voltage cable for the connection cable for the optional sensor in the flush mounted box Insert the prepared flush mounted box into the wall openin...

Page 26: ...ing the power supply cable Do not lay live cables Lay the Fan BUS and power cables separately The installation and connection must only be performed by qualified and trained personnel Filler for installing the box deep flush mounted plasterboard wall box min 87 mm insulated terminal lustre terminal Requirements The wall openings are created The cables are laid Break out a cable entry for the power...

Page 27: ...fans a 3 wire connecting cable is laid between the two boxes Fitting the fan BUS distribution box Filler for installing the box stripping tool terminal blocks 5 pole 3 x cover for the box e g cover in switch design Requirements The wall openings are created The fan cables and the fan connecting cable are laid Break out one cable entry per fan pair for the fan connecting cable in the flush mounted ...

Page 28: ...table filler Connect the fan BUS cables to terminal blocks 5 pole as follows The cable ends of the same colour of ventilation units in paired operation should be connected to the same pole of the terminal block Ö Ö A maximum of 4 poles are assigned with 2 cables each Attach the cable ends of the additional connecting cable 3 wire to the terminal block of the corre sponding colour Push the connecte...

Page 29: ... entry for the power supply cable at the bottom of the flush mounted box Break out a cable entry for the fan BUS connection cable for the connection cable for the optional sensor at the opening in the flush mounted box Insert the prepared flush mounted box into the wall opening Ö Ö Das Unterputz Schaltnetzteil ist angeschlossen Lay the power supply cable 230 V AC through the cable entry on the bas...

Page 30: ...sensor or to a home automation system follow the instructions in grey italics Stripping tool fan BUS connection cable 3 wire terminal blocks 5 pole 3 x Requirements The mounting box is fitted The switching PSU is connected Pull the lever on the lower right side of the operat ing unit backwards 1 Slide the base plate downwards as far as the stop 2 Ö Ö The operating unit is unlocked Screw the operat...

Page 31: ... Designation Colour I 24 V Operating voltage 24 V DC Red II GND GND Black III Lü1 Ground 1 GND White IV Ub Fan operating voltage Green V Lü2 Ground 2 GND Brown VI Sk1 External Interface optional sensors VII Sk2 24 V III IV V VI VII sMove s4 s8 with cabinet mounted PSU and sMove s4 mit flush mounted PSU Remove about 8 5 mm of insulation from each fan BUS cable Connect the fan BUS cables to terminal...

Page 32: ... observe information concerning pressure monitor page 17 NOTE If jumer 2 is set incorrect on the controller s rear side the controller does not fulfill the desired functions Observe the position of Jumper 2 Ö Ö The operating unit of the controller is installed Mount the operating unit behind the guides on the base plate Ensure that the vents are pointing upwards and downwards Ensure that the recei...

Page 33: ...cator light filter change indicator blue flashing 3 Operating mode button 4 Heat recovery mode orange indicator light filter change indicator orange flashing 5 Pause Off indicator light 6 Pause Off button 7 Output level indicator lights 8 Slide control 1 2 3 4 5 6 7 8 Slide control Briefly pressing the fan symbol allows you to select one of the four specific output levels Touching the slide contro...

Page 34: ... LED display time Significance permanent Heat recorvery mode set in pause function nach der Pause schaltet der Reg ler die Lüftungsgeräte in Wärmerückgewinnung flashing Filter change indication permanent Continuous ventilation mode set in pause function nach der Pause schaltet der Regler die Lüftungsgeräte in Durchlüftung flashing Filter change indication permanent OFF mode only standard version f...

Page 35: ...is in heat recovery mode Ö Ö The output level is 25 The sMove controller internally stores the last selected configuration of output level and operating mode After the controller has been switched off for example in the event of a power interruption the sMove controller switches on again in the last stored configuration A configuration is stored in the internal memory as soon as it was active for ...

Page 36: ...e controller is switched on Ö Ö You have selected the heat recovery mode Setting contiuous ventilation mode The ventilation unit s fan works without changing direction Thus no heat recovery takes place in this mode The continuous ventilation unit must be set to supply air mode This mode is recommended for cooling the room during summer nights Requirement The controller is switched on Ö Ö You have ...

Page 37: ...y or continuous ventilation mode Press the button Pause duration one time 1 hour two times 2 hours three times 4 hours four times 8 hours Ö Ö The LEDs Pause Off and the corresponding LED left to the slide control are flash alternately 1 4 x The pause can be overridden at any time by selecting a different output level Ö Ö You have set the selected pause duration 1 h 2 h 4 h 8 h If the controller is...

Page 38: ...oller is in heat recovery or continuous ventilation mode Ö Ö You have shut off the controller Press the button longer than 5 seconds Ö Ö The white Pause Off indicator light is perma nently lit Display of remaining pause time If the controller sMove is in pause the remaining time in which the controller is in pause can be viewed Requirements The controller is in pause function Press any button on t...

Page 39: ...s in heat recovery or continuous ventilation mode Ö Ö You have set an predefined output level Set continuous output adjustment Requirement The controller is in heat recovery or continuous ventilation mode Ö Ö You have set continuous output adjustment Press the button with the symbol matching the desired output level e g 3 Fan output 100 level 4 Fan output 50 level 3 Fan output 35 level 2 Fan outpu...

Page 40: ...n for at least 5 seconds Ö Ö The upper LED on the left side of the slide control flashes in white 6 5 Confirm filter change After 180 days the necessary filter change is indicated by a continuously flashing light next to the operating mode button The colour is defined by the current operating mode Continuous ventilation mode is active blue LED flashes Heat recovery mode is active orange LED flashe...

Page 41: ...umber of running lights corresponding to the end value will move towards the end value The display disappears between the individual numbers Requirement The controller is switched on Ö Ö You have requested the days of operation for the controller Example Number s position Indicator light Digit first place left of the pause button 0 second place End value 4th indicator light to the left of slide co...

Page 42: ...necessary cleaning or maintenance work can be carried out by the user by following these instructions Detergents NOTE The plastic glass surface of the inner panel controller is not scratch resistant and may be damaged Do not use sand soda acid or chlorine based cleaning agents A commercially available detergent in warm water can be used for cleaning The following tools may be used for cleaning lin...

Page 43: ...re C 5 50 Dimensions W x H x D in mm 86 x 86 x 24 Conformity 9 Scope of supply Überprüfen Sie die Lieferung bei Erhalt anhand des Lieferscheines auf Vollständigkeit und Transportschäden Reklamieren Sie fehlende Positionen unverzüglich sMove operating unit white Switching PSU Accessories pack incl terminal blocks Jumper manual Component Item number sMove controller s4 incl cabinet mounted PSU 1003 ...

Page 44: ...04 0145 Hygrostat HYG18 1002 0044 Hygrostat HYG12 1002 0015 Flush mounted box 60x66 3002 0244 Flush mounted box 60x90 1003 0104 Plasterboard wall box 61x68 1003 0084 Wall installation box 70x87 1004 0084 Round cable LiYY O 3x0 75 33m 1004 0020 Spare parts Component Item number Control panel switching PSU NT17 s4 3002 0274 Flush mounted switching PSU NT17 s4 3002 0273 Control panel switching PSU NT...

Page 45: ...ct if necessary Controller does not function Operating unit is incorrect ly not connected Check wiring No electrical contact Check cables Ensure cables are stripped sufficiently approx 8 5 mm Indicator lights do not light up Faulty controller Replace controller There is no power Check power supply Slide control defective Replace controller Disassembly and disposal Dissassemble the controller in th...

Page 46: ...ture product wear Further information about the warranty is available at www inventer eu warranty 13 Service Claims Check the delivery for completeness and transport damage upon receipt using the delivery note Report missing items immediately and at the latest within 14 days to your supplier distributor or factory representative Warranty and guarantee claims In the case of a warranty or guarantee ...

Page 47: ... 0 36427 211 0 FAX 49 0 36427 211 113 E MAIL INFO INVENTER DE WEBSITE WWW INVENTER DE CEO ANNETT WETTIG VAT ID NUMBER DE 815494982 JENA DISTRICT COURT HRB 510380 PICTURE CREDITS INVENTER GMBH 2014 19 ALL RIGHTS RESERVED INVENTER GMBH 2014 19 SUBJECT TO MODIFICATIONS ALL INFORMATION IS SUPPLIED WITHOUT GUARANTEE NO LIABILITY IS ACCEPTED FOR PRINTING ERRORS COMPANY DETAILS ...

Page 48: ...Version 04 2019 Subject to changes Article number 5021 0016 inVENTer GmbH 2014 19 www inventer eu inVENTer GmbH Ortsstraße 4a D 07751 Löberschütz 49 0 36427 211 0 49 0 36427 211 113 info inventer de ...

Reviews: