ELECTRICAL CONNECTIONS
sMove controller
•
Installation and operation manual
3.4
Jumper
Jumper 2
1)
is used to assign functions to the external interface when a potential-free switching
contact is connected (pressure monitor: Opener (normally closed NC) / other sensors: Closer
(normally open NO) and for integration into a house control system.
The position of the jumper may only be changed in a voltage-free state.
Function assignment depending on switching contact
NO (Closer)
NC (Opener)
Sensor
Position of Jumper 2
Function at switch actuation / switching
attached
Normal operation
OFF
(fireplace function)
Opener:
Pressure mo-
nitor (4 Pa)
not
attached
Continuous ventilation
Output level 3
Normal operation
Closer:
Hygrostat
CO
2
VOC
Interface used as analogue input
The 2-pin plug for jumper 2 is located on the rear side of the operating unit. The jumper 2 is not
plugged in at the factory and is located inside the accessories pack of the controller. It must be
attached if necessary. Jumper 1 is used for service settings and must be left as delivered to
ensure correct functioning of the controller.
If a pressure monitor with normally open contact is connected, e.g. if the sMove controller is exch-
anged, it must be configured as a normally closed contact (switch with changeover contact) or, if
this is not possible, it must be replaced by a pressure monitor with normally closed contact.
It is not possible to connect a potential-free switch and an analogue input simultaneously. A
connected analogue input always has priority over a potential-free switching contact. If a pres-
sure monitor is connected, the pressure monitor has priority to other connected sensors.
If Jumper 2 is not attached and the sMove controller is integrated into an home automation
system, the following direct voltages must be set:
Function
Control voltage [V DC]
Ventilation output level 3
0.00 V
≤ U ≤ 0.25 V
Ventilation output level 4
0.75 V
≤ U ≤ 1.25 V
Ventilation output level 2
1.75 V
≤ U ≤ 2.25 V
Ventilation output level 1
2.75 V
≤ U ≤ 3.25 V
OFF
3.75 V
≤ U ≤ 4.25 V
Heat recovery output level 1
4.75 V
≤ U ≤ 5.25 V
Heat recovery output level 2
5.75 V
≤ U ≤ 6.25 V
Heat recovery output level 3
6.75 V
≤ U ≤ 7.25 V
Heat recovery output level 4
7.75 V
≤ U ≤ 8.25 V
2
2
2
2