31
INSTALLATION AND ASSEMBLY
sMove controller
•
Installation and operation manual
NOTE:
Incorrect connection of the termi
-
nals on the rear side of the operating unit.
sMove or attached devices do not function!
• Ensure that the terminal assignment when
connecting the cables is correct. (
4.3:)
►
Attach the
• Operating voltage cable (red, + / black, –)
to the two upper terminals of the terminal block,
5-pole;
• Fan-BUS wires to the three lower terminals of the
terminal block, 5-pole,
•
connecting cable for the optional sensor, 2-wire,
to the terminal block, 2-pole,
on the rear side of the operating unit.
Terminal Designation
Colour
I
+ 24 V
Operating voltage
24 V DC
Red
II
GND
GND (–)
Black
III
Lü1
Ground 1 (GND –)
White
IV
Ub+
Fan operating voltage
Green
V
Lü2
Ground 2 (GND –)
Brown
VI
Sk1 (+)
External Interface
(optional sensors)
VII Sk2 (–)
+ 24 V
–
III (–)
IV (+)
V (–)
VI (+)
VII (–)
sMove s4/s8 with cabinet mounted PSU and
sMove s4 mit flush-mounted PSU:
►
Remove about 8.5 mm of insulation from each
fan-BUS cable.
►
Connect the fan-BUS cables to terminal blocks,
5-pole, as follows:
The cable ends
• of the same colour
• of ventilation devices in paired operation
should be connected to the same pole of the
terminal block
Ö
A maximum of 4 poles are assigned with
2 cables each.
►
Attach the cable ends of the additional connecting
cable, 3-wire, to the terminal block of the corre-
sponding colour.
►
Push the connected terminal blocks into the box.