295
NS3503-16P-4C User Manual
30~60 watts
High Power Speed Dome
This state-of-the-art design is considerable to fit in various network
environments like traffic centers, shopping malls, railway stations,
warehouses, airports, and production facilities for the most demanding
outdoor surveillance applications. Electrician is not needed to install AC
sockets.
Note
:
Since the NS3503 UPoE Switch Series per PoE port supports 52V/54V DC PoE power output, please
check and assure the Powered Device’s (PD) acceptable DC power range is 50V~54V DC; otherwise, it will
damage the Powered Device (PD).
In a power over Ethernet system, operating power is applied from a power source (PSU-power supply
unit) over the LAN infrastructure to powered devices (PDs), which are connected to ports. Under some
conditions, the total output power required by PDs can exceed the maximum available power provided
by the PSU. The system with a PSU is capable of supplying less power than the total potential power
consumption of all the PoE ports in the system. In order to maintain the function of the majority of the
ports, power management is implemented.
The PSU input power consumption is monitored by measuring voltage and current .The input power
consumption is equal to the system’s aggregated power consumption .The power management concept
allows all ports to be active and activates additional ports, as long as the aggregated power of the
system is lower than the power level at which additional PDs cannot be connected .When this value is
exceeded, ports will be deactivated, according to user-defined priorities. The power budget is managed
according to the following user-definable parameters: maximum available power, ports priority and
maximum allowable power per port.
Reserved Power
There are five modes for configuring how the ports/PDs may reserve power and when to shut down
ports.
Allocation mode
In this mode, the user allocates the amount of power that each port may reserve. The
allocated/reserved power for each port/PD is specified in the Maximum Power fields. The ports are
shut down when total reserved power exceeds the amount of power that the power supply can
deliver.
Note
: In this mode, the port power is not turned on if the PD requests more available power.
4.15.3 Power over Ethernet Configuration
This section allows the user to inspect and configure the current PoE configuration setting as screen in
Figure 4-16-1 appears.