Installation and programming manual
Maintenance
63
Chapter 15
Maintenance
The following operations must be carried out regularly.
1. Using a damp lint-free cloth, remove any dust that may have gathered on the control panel (do not use
any kind of cleaning product or solvent!).
2. From panel: press
<key>, Test LED, Ok
to test the LEDs.
3. Check the battery efficiency and change them if necessary.
4. Check the integrity of all wires and connections.
5. Ensure that there are no insects inside the control panel.
6. Carry out maintenance on the detectors (clean the outside and the detection chamber).
Note:
Points 1 and 2 can be carried out by authorized persons, whereas all other points must be carried out by
qualified technicians.
15.1 Set Time and date
From panel with the jumper inserted:
<key>, Settings, Date & Time
Navigate through the programming field and set the new values. The system will select the day of the week
automatically.
15.2 Viewing events
The system displays information regarding real-time events of major importance and disregards those of
minor importance (e.g.: if the system is dealing with three fault events when a pre-alarm event occurs, the
fault events will be disregarded and cleared from the display and the pre-alarm will take priority). All
events are saved to the log and can be viewed.
15.2.1 Signaling on the display
If several events of the same type occur, only the first will be shown on the display. If several alarms occur,
the first alarm will remain on the first line of the display and the most recent alarm will be shown on the
line below.
To view the events on the display, press button
or
.
15.2.2 Viewing the events log
Press
<key>, View log, Ok
: all the recorded events (maximum 100) can be viewed in chronological order.
15.3 Day/Night mode
15.3.1 Day
There are people in the building, therefore, those in charge of the safety of the building and its occupants
should be duly informed before the evacuation command is given.
Silence
Silences (turns Off) the panel beeper and silenceable outputs. The Silence command will be
undone automatically, if a new alarm event occurs (e.g.: another detector signals alarm
conditions).
Pre-alarm
Some points can be programmed to signal pre-alarm status. If no-one intervenes during the
pre-alarm phase, the system will generate an alarm when the programmed pre-alarm time
expires. Refer to
paragraph 9.2.2 - Detection line parameters
to enable/disable the pre-
alarm time of points.