Installation and programming manual
Programming from panel
49
SPRINKLER
The line will operate as a resettable alarm line (it will remain active for the duration of the
alarm condition). Activation of the line will generate a fire alarm and the display will indicate
activation of the “Sprinkler” system. The line will also generate the “Sprinkler” signal that can
be used for the activation of specific outputs which provide separate signals.
Modify levels
As above.
Short=Alarm
As above.
Night prealarm
As above.
Pre-alarm
As above.
Filtered
As above.
SUPERVISORY
The line will signal a specific fault condition and will activate Fault and Supervision signals that
can be used for the activation of specific outputs.
Modify levels
As above.
Short=Alarm
As above.
Filtered
As above.
GAS RELAY
The line will interface gas detectors with output relay (see the respective diagram). Pre-alarm
activation will generate a pre-alarm gas signal, if the pre-alarm clears (restores to standby),
the control panel will stop signalling. In the event of alarm activation, the control panel will
signal a gas alarm.
Modify levels
As above.
Reset.Alarm
If you select "Yes", alarm signalling will cease when the value returns below
the set threshold; otherwise alarm signalling will persist until the next reset
operation occurs.
Filtered
If this option is enabled, an alarm or fault condition on the line will be
activated only when it persists for a period of time longer than the pre-set
“Filter Time”.
Passing
If this option is enabled, the line will be activated with no alarm signalling;
useful for CO gas detection in parking areas.
EXTINGUISH
The line will be used to command the extinguishment board functions. The type of command
that is achieved by activating the line can be set on the two lines that follow. The available
functions are: Disable extinguish; Disable manual extinguish; Disable automatic extinguish;
Confirm extinguish; Manual extinguish; Stop extinguish. For further details regarding the
previously mentioned functions, refer to the extinguishant board section.
Modify levels
As above.
Short=Alarm
As above.
Filtered
As above.