54
Programming from panel
Conventional fire detection control panel
9.4
Setting holidays
From panel: <key>, Programming,
Progr. Holidays
, select a holiday,
Ok
This option will allow you to set specific periods which determine exceptions with regard timer
programming, for example, holidays, bank holidays, etc. Navigate through the programming field and set
the new values.
9.4.1 Holidays parameters
9.5
Setting the control panel options
From the panel:
<key>, Programming, Options
Navigate through the programming field and set the new values.
9.5.1 Options
Start/End time 2
Hour and minutes of the Start and End of the interval 2.
Day, Month, Year
Operational date of the timer. To indicate any day, month or year, leave “--” (for example,
every 3rd of the: day=3, month = “--”, year = “--”).
Sunday, etc.
Day of the week for weekly arrangements.
Valid only when the “Day”, “Month”, “Year” are set as “--”.
Holidays
If you select "Yes" the timer will activate during the programmed holiday periods (refer to
paragraph 9.3 - Setting the Timers
).
NO Holiday
If you select "Yes", the timer will not activate during holiday periods; this option has priority
over the previous two options.
Force night
Activation of the timer will switch the panel to Night mode. The panel cannot be switched back
to Day mode until the set timer interval expires. Once the set timer interval expires, the panel
can be switched back to day mode either by another timer or manually from the panel (refer
to
paragraph 15.3 - Day/Night mode
).
Set day
Activation of the timer will switch the panel to Day mode. The panel can be switched back to
Night mode either by another timer or manually from the panel.
Set night
Activation of the timer will switch the panel to Night mode. The panel can be switched back to
Day mode either by another timer or manually from the panel.
Disable zone
On activation the timer will bypass the specified zone.
Enable zone
On deactivation, the timer will unbypass the selected zones.
Disable verif.
When the timer is activated, the alarm verify is disabled on the selected zone.
Zone
List of zones to be bypassed on timer activation (zones set as "YES" will be bypassed).
Holiday nn
Number of holidays (maximum 15), already preset.
day, month,
year
Date of the holiday or start date of the holiday period. To indicate any day, month or year, leave “-
-” (for example, every 3rd of the: day=3, month = “--”, year = “--”).
Sunday, etc.
Day of the week for weekly arrangements.
Valid only when "Endurance"=1 and "Day", "Month", "Year" = “--”.
Duration
Length of time (expressed in days) of the holiday period (0 at default). If you set 0, the system
will not take the holiday into account.
Mains failure delay
This is a programmable delay (0 to 30 minutes) which runs between the start of the
mains failure event and the actual fault signal. This delay avoids unnecessary signalling of
brief 'Mains failure' events.
Delay dialler
The period (0 to 10 minutes) which the dialler allows before signalling a zone alarm.
If an alarm is activated from a manual call point or by means of the
EVACUATE
button,
the output will activate immediately.