Installation and programming manual
Overview
5
Chapter 1
Overview
Note:
The control panels described in this manual have been designed and manufactured to the highest standards
of quality, reliability and performance adopted by INIM Electronics. The components selected for these
products will operate properly within their specifications when the environmental conditions outside the
product enclosure comply with Class 3k5 (EN60721-3-3.).
Danger:
The GAS control function is not provided for in the aforesaid standard and therefore cannot
be considered EN54-2 compliant.
Danger:
In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance with EN54-
2, all the manual alarm buttons and fire detectors employed in the system must be
associated with fire detection and alarm functions.
1.1
Application and use
The SmartLine conventional fire control panel manages up to 20 conventional detector lines (zones) for
SmartLine020 models or up to 36 lines for SmartLine036 model. Each line (zone) accepts up to 30 devices
and is provided with an additional I/O line that can be configured as an open-collector output (the
activation principles can be defined during the configuration phase) or as an independent input line
(separate from the zone) for fire detection, gas detection line, etc. The basic model has 4 on-board zones
(2 for the SmartLine020-2 model) expandable to 20 (or 36 for the SmartLine036) by means of 2
SmartLine/8Z optional attachment boards (8 lines per board).
The control panel also provides a series of outputs for the activation of signalling or remote transmission
devices. The graphic display and LEDs provide visual indication of the system status and real-time
signalling of fault conditions. The control panel supports up to 4 repeater panels (SmartLetUSee/LCD-Lite);
these remote consoles replicate all the information provided by the control panel and allow access to level
1 and 2 functions. The control panel can also house and manage the SmartLetLoose/ONE gas extinguishant
boar (optional).