Programming from panel
Conventional fire detection control panel
9.2.3 I/O detection line parameters
<aaaaaaaaaaaaa>
Zone Description (e.g.downstairs kitchen). The field cannot be edited at this point. If you wish to
change the string, you must step back to the previous menu.
Line type
Using the
Ok
key, scroll the various programming options for the I/O line:
OUTPUT ZONE STA-
TUS
In this mode, the line will operate as an Open-Collector output that will activate in response to any
of the selected signals ("Alarm", "Pre-alarm", "Gas alarm", "Gas pre-alarm", "Sprinkler",
"Supervisory", "Class Change" and "Fault") relative to the control panel (if the "Panel" option is
selected from the following list ), or relative to the zones specified in the list (All zones set as
“YES”).
Silenceable
If “YES” is selected, it will be possible to switch Off the activated output by
inserting the key and pressing the
SILENCE
button.
Inverted
If selected, the output will always be closed to ground and will open when
activated.
Duration
-- min -- sec
Activation time (0 to 10 minutes); if the endurance is not defined (“--”) the
output will not deactivate. Under all circumstances, if the condition clears the
output will deactivate.
At least 1 / 2 /
All
The output will activate if one or more signals activates on at least one/two/
all of the selected zones.
OUTPUT DISABLE-
MENTS
In this mode, the line will operate as an Open-Collector output that will activate when any of the
control panel components is bypassed (if "Panel" option is selected), or when one or more zones
(all the zones set as “YES”) are bypassed.
Silenceable
As above.
Inverted
As above.
Duration
-- min -- sec
As above.
At least 1 / 2 /
All
The output will activate if at least one/two/all of the selected zones are
disabled.
OUTPUT EXTINGUISH
In this mode, the line will operate as an Open-Collector output that will activate in response to the
selected extinguishant module signals: "Disable manual"; "Disable automatic"; "Pre-extinguish";
"Extinguish"; "Confirm extinguish"; "Pressure Switch".
Silenceable
As above.
Inverted
As above.
Duration
-- min -- sec
As above.
OUTPUT SIGNALS
In this mode, the line will operate as an Open-Collector output that will activate in response to the
selected conditions: (“Reset”, “Day”, “Night”).
Silenceable
As above.
Inverted
As above.
Duration
-- min -- sec
As above.
OUTPUT TIMERS
In this mode, the line will operate as an Open-Collector output that will activate in response to the
activation of the specified timers (i.e. all timers set as “YES”).
Silenceable
As above.
Inverted
As above.
Duration
-- min -- sec
As above.
OUTPUT EQUATIONS
In this mode, the line will operate as an Open-Collector output that will activate when at least one
of the specified equations is satisfied (all the equations set as “YES”).
Silenceable
As above.