22
User interface
Conventional fire detection control panel
[R]
TEST
(yellow)
Indicates test status on
one or more zones.
A zone in test status cannot generate
alarms or signalling of any kind. However,
the respective LED will turn on for several
seconds and then reset and turn off
automatically. The ALARM NAC output will
activate for approximately 3 seconds to
confirm that the device is working properly.
This feature allows technicians to carry out
point/zone tests and inspections alone, as
it eliminates the need of constantly
returning to the panel to verify/reset the
events generated by the points.
[S]
ON
(green)
Indicates that the
system is operating
(On).
This LED will go Off in the event of joint
primary (230V
) and secondary
(batteries) power failure.
[T]
DIALLER ON
(red)
Indicates that the dialler
activation output is
active.
Indicates that the alarm
communication has been
sent successfully.
The dialler will be activated (after the pre-
set delay) in the event of an alarm.
[U]
DISABLE/
FAULT ALARM
DIALLER
(yellow)
Indicates that the dialler
activation output for
alarm signalling is
disabled or faulty, the
display will provide
further details.
Indicates restoral of a
fault event. This
condition can be cleared
by reset only (level 2).
[V]
DISABLE/
FAULT BELLS
(yellow)
Indicates that the
sounder/flasher
activation output is
disabled or faulty—the
display will provide the
respective details.
Indicates restoral of a
fault event. This
condition can be cleared
by reset only (level 2).
[W]
DISABLE/
FAULT FAULT
DIALLER
(yellow)
Indicates that the dialler
activation output for
fault signalling is
disabled or faulty, the
display will provide
further details.
Indicates restoral of a
fault event. This
condition can be cleared
by reset only (level 2).
[X]
NIGHT MODE
(yellow)
Indicates that the panel
is operating in night
mode.
For safety reasons, the pre-alarm time of
all points is cancelled automatically during
night mode (night mode pre-alarm time =
0 seconds). As a further safety precaution,
the system can be silenced for the pre-set
SILENCE time only. Night Mode should be
applied when no or few persons are
present or awake in the building, and the
building security is the responsibility of a
night watchman or security patrol guard
who is present or notified by the dialler.
Extinguishant board signals (optional system enhancement device)
[Y]
DISABLE
EXTINGUISH
Indicates disablement of
all types of extinguish
commands, via the
appropriate key
(
paragraph 5.1 - [G]
).
[Z]
DISABLE
AUTO
Indicates disablement of
automatic extinguish
commands, via the
appropriate key
(
paragraph 5.1 - [H]
).
LED
If On solid:
If Blinking:
Note