Ensure the momentary remote start switch is not
stuck closed. To start a machine press the remote
start switch for no more than 2 to 5 seconds.
Emergency Stop
Xe Software Logic for R & RS machines:
This will occur when the emergency stop button is
engaged.
Recommended Checks
The remote stop switch is a 24 VDC signal on P3
terminal in the controller. An open switch will show
this alarm. Check for loose/broken wiring. Broken
switch.
Ensure switch is reset. Check for loose wires.
High Coolant Filter Pressure Drop
Xe Software Logic for R & RS machines:
This will occur if the compressor has been running
loaded for at least 8 seconds, is warmed up, already
Summary of Contents for Xe-145M