Is the overload set properly according to the motor
amperage found in the motor data tag? See Tech
Note 8557.
Are the running amps balanced according to Tech
Note 2297?
The wires of the fan overload are connected to P3
terminal. Check wiring and P3 terminal connector.
Is ductwork installed causing an air restriction?
If the machine has a blower drive installed, install
an LCP or HIM to read the fault log of the drive.
Megger the motor
Remote Stop Failure
Xe Software Logic for R & RS machines:
Will occur if the remote start/stop option is enabled, the
remote stop button remains open and either start
button is pressed. The remote stop switch is normally
closed.
Recommended Checks
Ensure the connection in P3 terminal of the remote
stop circuit is closed: 0 volts DC across the 2