Recommended Checks
Read the alarm from the blower drive (not the
general alarm in the Xe controller) and troubleshoot
according to the fault code/number found in Tech
Direct.
Is the blower drive incoming voltage balanced to
ground? If not, correct.
Disconnect motor leads from the blower drive
output. If the blower drive shows running, perform
Megger/Milliohm on the blower motor.
P3 Terminal connection is the one receiving the
drive status alarm. Check for good connections.
Ensure the ductwork of the machine is properly
sized not creating airflow restriction = high amps.
High Ambient Temperature
Xe Software Logic for R & RS machines:
A:
Will occur if the Enable Ambient Monitoring set point
is ON, the compressor has been in the Run-Starting
state for greater than 5 seconds, or is in the Run-
Unload Normal, Run-Unload Forced, Run-Load, or
Stopping state and the package inlet temperature