P5 Electrical Schematic Connection
R-Series RS-Series
1AVPT Inlet Vacuum
Connected to P5, 1AVPT has a range of 0 to 15 psi (0 -
1.03 Bar). The output signal to the controller is 0.5
VDC at 0 psi (0 Bar) and 4.5 VDC at 15 psi (1.03 Bar).
Inlet vacuum differential pressure is monitored to
ensure the inlet air filter health and the butterfly valve in
the inlet valve assembly is open when the machine
loads (if the inlet valve is not open when the machine