dryer will continue to run. The condition must exist for
at least 180 seconds before the warning will occur.
Recommended Checks
High ambient temperature (if air cooled).
Dirty condenser (if water cooled).
High inlet air temperature.
High airflow rate.
Condenser fan operation.
Refrigerant charge.
Defective pressure sensor.
Condenser Temperature Low
Xe Software Logic for R & RS machines:
This will occur if the condenser sensor has a value
below the low temperature threshold while the dryer is
running, on compressors with the integrated dryer. This
is not a dryer fault. If this happens, the compressor and
dryer will continue to run. The condition must exist for
at least 180 seconds before the warning will occur.
Recommended Checks