case the power quickly returns. A phase monitor is
something that can cause this trip.
Recommended Checks
Check/reset MCB3 circuit breaker. If trips again
there is a shorted/grounded component. Remove
all the components from P1 terminal with the
exception of the hot 120 VAC and ground cable. Re
connect the components to see which one is
causing the trip (troubleshoot by elimination
technic)
E-stop wiring needs to be close to allow control
voltage to P1-1 terminal.
Possible condensate drain short/ground.
1ATS HAT switch circuit open.
K2 circuit breaker open.
LVM low voltage monitor tripped.
Solenoid shorted/grounded tripping MCB3 circuit
breaker.
Broken wire or defective quick connector plug.