The last nine System Diagnostics are informational. If any of them indicate a Warning condition, then
the
i
³C Lite
can still enter and remain in Run mode, but the problem should be investigated and
corrected.
User Graphics
Ok
= Application graphics objects loaded successfully
Fault
= Application graphics objects not loaded, or load failed
W-Dog Trips
0
= Watchdog timer has not tripped since the last power-up
x
= Number of times watchdog timer has tripped
Net Errors
0
= No CAN network bus-off errors have occurred
x
= Number of CAN network bus-off errors that have occurred
Network State
Ok
= At least one other node was found on the CAN network
Warning
= No other nodes were found on the CAN network
Network ID
Ok
=
This node’s CAN Network ID is in the ran
ge 1 to 253
Warning
= This node’s CAN Network ID was out of range a
t power-up
Dup Net ID
Ok
= This node’s Network ID is unique on the CAN network
Warning
= This node’s Network ID is duplicated in another node
Clock Error
Ok
= Time and date have been set
Warning
= Time and date need to be set
I/O System
Ok
= I/O configuration matches the installed I/O and COM modules
Warning
= I/O configuration needs updating to match installed modules
Battery
Ok
= Backup battery operating properly
Warning
= Backup battery needs to be replaced
Summary of Contents for i3C Lite
Page 1: ......
Page 8: ...Page 8 ...
Page 65: ...Page 65 Figure 9 3 Screen Calibration ...
Page 78: ...Page 78 Figure 11 2 Relay and Digital Output ...
Page 82: ...Page 82 Figure 11 5 Digital Input ...
Page 86: ...Page 86 11 9 RTD Wiring on J3 Connector ...
Page 110: ...Page 110 Figure 13 8 Alarm Configuration in i Config ...
Page 167: ...Page 167 ...