Page | 42
8.5
Scan List
This can be accessed from the Scan List button on the Protocol Config screen or the Mapping button
on the Device List screen and provides a Scan List of the Data Mapping entries. To transfer data
between the I³ and remote target, a Scan List must be created that defines each transaction. Each
mapping entry (transaction) contains the source and destination registers, the number of
consecutive registers transferred, the direction of the transfer and what triggers the transfer.
Typically, the number of entries is
limited to 512
.
NOTE
: The order of the Scan List is the order in which the transactions occur. Sort functions are
provided to change the order of the list. Each entry also has an identifying index. If the device status
register is enabled and a transaction failure occurs, the status register indicates the index number of
the transaction that has failed.