44
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
Thermal regulation “
term
”
Menu item
Description
Adjustment
range
Default
value
sest
External probe
enabling
Allows to choose and enable an external probe.
0 no probe
1 pdc probe
2 boiler probe
1
r1mi
Zone 1 minimum
heating setting
Without the external probe it defines the minimum flow temperature that can be set
by the user. With the external probe present it defines the minimum flow temperature
corresponding to operation with maximum external temperature
25 ÷ 50 °C
25 °C
r1mA
Zone 1 maximum
heating setting
Without the external probe it defines the maximum flow temperature that can be set
by the user. With the external probe present it defines the maximum flow temperature
corresponding to operation with minimum external temperature
30 ÷ 80 °C
55 °C
r2mi
Zone 2 minimum
heating setting
Without the external probe it defines the minimum flow temperature that can be set
by the user. With the external probe present it defines the minimum flow temperature
corresponding to operation with maximum external temperature
25 ÷ 50 °C
25 °C
r2mA
Zone 2 maximum
heating setting
Without the external probe it defines the maximum flow temperature that can be set
by the user. With the external probe present it defines the maximum flow temperature
corresponding to operation with minimum external temperature
30 ÷ 80 °C
45 °C
r3mi
Zone 3 minimum
heating setting
Without the external probe it defines the minimum flow temperature that can be set
by the user. With the external probe present it defines the minimum flow temperature
corresponding to operation with maximum external temperature
25 ÷ 50 °C
25 °C
r3mA
Zone 3 maximum
heating setting
Without the external probe it defines the maximum flow temperature that can be set
by the user. With the external probe present it defines the maximum flow temperature
corresponding to operation with minimum external temperature
30 ÷ 80 °C
45 °C
remi
Minimum external
temperature in
heating stage
With the external probe present it defines at what minimum external temperature the
system must operate at the maximum flow temperature
- 20 ÷ 0 °C
-5 °C
remA
Maximum external
temperature in
heating stage
With the external probe present it defines at what maximum external temperature the
system must operate at the minimum flow temperature
5 ÷ 25 °C
25 °C
F1mi
Zone 1 minimum
cooling setting
Without the external probe it defines the minimum flow that can be set by the user.
With the external probe present it defines the minimum flow temperature corre-
sponding to operation with maximum external temperature
7 ÷ 20 °C
10 °C
F1mA
Zone 1 maximum
cooling setting
Without the external probe it defines the maximum flow that can be set by the user.
With the external probe present it defines the maximum flow temperature corre-
sponding to operation with minimum external temperature
10 ÷ 25 °C
13 °C
F2mi
Zone 2 minimum
cooling setting
Without the external probe it defines the minimum flow that can be set by the user.
With the external probe present it defines the minimum flow temperature corre-
sponding to operation with maximum external temperature
7 ÷ 20 °C
10 °C
F2mA
Zone 2 maximum
cooling setting
Without the external probe it defines the maximum flow that can be set by the user.
With the external probe present it defines the maximum flow temperature corre-
sponding to operation with minimum external temperature
10 ÷ 25 °C
13 °C
F3mi
Zone 3 minimum
cooling setting
Without the external probe it defines the minimum flow that can be set by the user.
With the external probe present it defines the minimum flow temperature corre-
sponding to operation with maximum external temperature
7 ÷ 20 °C
10 °C
F3mA
Zone 3 maximum
cooling setting
Without the external probe it defines the maximum flow that can be set by the user.
With the external probe present it defines the maximum flow temperature corre-
sponding to operation with minimum external temperature
10 ÷ 25 °C
13 °C
femi
Minimum external
temperature in
cooling phase
With the external probe present it defines at what minimum external temperature the
system must operate at the maximum flow temperature
20 ÷ 35 °C
25 °C
femA
Maximum external
temperature in
cooling phase
With the external probe present it defines at what maximum external temperature the
system must operate at the minimum flow temperature
25 ÷ 40 °C
35 °C
ESC
Output
exit menu
-
Heating / cooling system configuration menu “
ConF
”
Menu item
Description
Adjustment range
Default
value
S201
Zone 1 control device selection
0 = remote zone control
1 = Room probe
2 = Room thermostat
3 = Room thermostat plus zone remote
control
4 = Remote panel supplied with Audax
Top
5 = Remote panel supplied with Audax
Top plus room thermostat
0
S202
Zone 2 control device selection
2
S203
Zone 3 control device selection
2
Summary of Contents for 3.025499
Page 1: ...MAGIS HERCULES ERP IE Instruction and recommendation booklet 1 038684ENG ...
Page 2: ......
Page 39: ...39 3 3 2 2 INSTALLER USER MAINTENANCE TECHNICIAN ...
Page 66: ...66 ...
Page 67: ...67 ...