Communication parameters
Menu item
Description
Adjustment range
Default value
Addr
address
Allows to adjust the address of the remote zone control
1 = main zone remote control
22 = zone 2 remote control
23 = zone 3 remote control
1
bAud
communication
speed
Allows to set the communication speed between the
boiler and the remote zone control
0 = 4800 bps
1 = 9600 bps
2 = 19200 bps
Zone 1 = 2
Zone 2 and
3 = 1
bLbe
Display lighting
Allows to set the display operation mode
0 =
1 =
2 =
0
bLIn
Light intensity
Allows to set the light intensity
0 ÷ 5
4
PCaL
Probe calibration Allows to calibrate the temperature probe in the remote
zone control
- 15 ÷ 15 K
0
CnSt
Display contrast
Allows to adjust the display contrast
0 ÷ 15
15
bu_d
buzzer
Allows to adjust the buzzer of the remote zone control
0 = on
1 = off
0
PSu1
Pwd
Password to change the internal communication param-
eters
(do not change)
0 ÷ 999
22
P_In
Initialisation by-
pass
Setting the parameter with a value other than zero
allows to prevent the initialisation of the remote zone
control when it is powered
(do not change)
0 ÷ 1
1
year
Year
Set the year
0 ÷ 99
0
Mont
Month
Set the month
1 ÷ 12
1
mday
Day
Set the day of the week
1 ÷ 31
1
uday
Day / week
Set the day of the week
1 ÷ 7
6
hour
Time
Set the hours
0 ÷ 23
0
mins
Minutes
Set the minutes
0 ÷ 59
0
3.11 PROGRAMMING THE REMOTE
ZONE CONTROL PARAMETERS.
By simultaneously pressing and holding the
buttons “ ” and “ ” one can access the com-
munication parameters programming menu; to
access it one must enter the access code “22”.
To enter the access code turn the main selector
clockwise until reaching the access code, then
press the main selector to access the menu.