IGBT D
IMMER
R
ACKS
Installation
& Operation
49
ILS Terminal
Name
XLR Pin
Name
WE Color Code
(e.g. Belden #8132)
IECA Color
Code
Belden Std.
Color Code
CATEGORY 5
Color Code
GND
1
Drain (Shield)
Drain
(Shield)
Drain
(Shield)
Brown (8)
White/Brown (7)
DMX -
2
White w/ Blue
Black
Black
(of Red Pair)
Orange (2)
DMX +
3
Blue w/ White
White
Red
White/Orange (1)
TALK -
4
White w/ Orange
Red
Black
(of White Pair)
Green (6)
TALK +
5
Orange w/ White
Green
White
Green/White (3)
Contractor is Responsible for All Terminations *
1) Only approved EIA-485 cable types may be used. Approved types include:
Belden #8132 or #9842
Alpha #3492C or #6413 TMB Proplex #PC224T
No plenum rated EIA-485 types are available. An acceptable plenum rated EIA-422 cable close enough in properties is: Belden #88102
ote
: No other EIA-422 cables are acceptable.
2) Category 5 cable may be used for DMX512. Approved types include: Belden #1583A and Belden #1585A (Plenum).
3) Cable MUST be terminated exactly as shown here.
4) DMX512 cable runs MUST be routed in a "Daisy-Chain" configuration as shown in your drawing set, if provided. DO NOT con-
vert these cables to home runs.
5) DMX512 cable runs should all be in metal conduit. Runs in exposed areas must be in metal conduit. Maximum cable run should
not exceed 1500 feet (preferred maximum 1000 feet).
* Factory Service Representative will terminate DMX512 wiring during engineering check-out (see
Engineering Check-Out
Request Form
at the end of this manual).
L
YTEMODE
®
ILS N
ETWORKS
Pin Number
Signal Name
Shielded Cat5e Wire Color
(Belden #1624 R or P)
1
Data +
White w/ Orange
2
Data -
Orange
3
SHIELD
Shield
4
+ 24 VDC
White w/ Green
5
Signal GND
Green
6
+ 24 VDC
White w/ Blue
7
Signal GND
Blue
8
+ 24 VDC
White w/ Brown
9
Signal GND
Brown
Contractor is Responsible for All Terminations
1) Only approved cable types may be used. Approved types include: Belden #1624R and Belden #1624P
2) Cable MUST be terminated exactly as shown here. Total length of cable in ILS Station Network Wiring must NOT exceed 2000
feet.
3) Cable runs should be routed in a "Daisy-Chain" configuration as shown in your drawing set, if provided. DO NOT convert these
cables to home runs. "Star" wiring is only allowed with short (50 foot) stubs or with use of an ILS Network Power Supply and only
as shown in your drawing set.
4) Maximum station quantity subject to power supply and system requirements. Please consult factory for specific information.
DMX512
Appendix A: Standard Wiring