Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Operation
AS-i telegram errors on the master
432
Diagnostics of
AS-i master 1
Safety Master 1
OK
130
ESC
Step 4:
AC1375: Menu screen not available.
►
If necessary, press [ ] to scroll to another master.
Slave List of
AS-i master 1
Safety Master 1
OK
130
ESC
Step 5:
AC1375: Menu screen not available.
►
Select AS-i master with [OK].
AS-i 1 diagnost.
Voltage Disturb.
Config. Error
OK
131
ESC
Step 6:
AC1375: Menu screen number = 72
►
Press [ ] to scroll to [Telegr. Error].
AS-i 1 diagnost.
Config. Error
Telegr. Error
OK
131
ESC
Step 7:
AC1375: Menu screen number = 72
►
Select [Telegr. Error] with [OK].
AS-i master 1
Telegr. Error Count.
0.4 %
48 / s
MORE
51
ESC
Step 8:
AC1375: Menu screen number = 29
> Dynamic display of AS-i telegram errors in per cent of the transmitted
telegrams.
> Dynamic display of AS-i telegram errors per second.
►
Scroll to the next screen with [MORE].