Main menu [Slave Setup]
110
7.9
Main menu [Slave Setup]
5481
Display or change the output data or parameters of individual slaves (password level 2 required).
WARNING
Risk of personal injury! Risk of material damage to the machine/plant!
After changing the slave outputs the output values remain unchanged.
The output values only change in the following cases:
Manual new setting of the outputs via Slave Setup,
when changing from projection mode to protected mode, unless the "slave reset" function was
deactivated via the menu,
host processes the outputs,
deactivate and restart the gateway.
►
Secure the concerned area.
►
Only trained personnel is allowed to set outputs manually.
►
Deactivate the outputs again immediately after the end of the test!
Menu tree
Explanation
Slave Setup
-- AS-i Master 1
> Display of the detected slave with the lowest address on the
bus.
►
Scroll through the addresses of the detected slaves with [ ] or [
].
►
Select slave address with [OK].
Slave Setup
-- AS-i Master 1
-- -- Digital output
> Display of current data of the selected slave
(
chapter Set output values (
→
page
)).
►
Change value of the output signal with [ ] or [ ] and then [SET].
> The line "Current" adopts the setup value and the change is
transferred to the outputs as long as the host does not process
these outputs.
►
Cancel with [ESC].
Slave Setup
-- AS-i Master 1
-- -- Parameter value
> Display of current parameter data of the selected slave
(
chapter Change slave parameter data (
→
page
)).
►
Change the value of the parameter in the "Setup“ line with [
] or [ ] and transmit it to the slave with [SET].
> If the value or change is not permissible:
"Slave data invalid" message.
►
Cancel with [ESC].
Slave Setup
-- AS-i Master 1
-- -- Analogue value
> Display of current data of the selected slave (depending on the
type of slave): analogue values
(
chapter Set output values (
→
page
)).
►
After [OK]: