Operation
Set output values
466
14.21
Set output values
Set digital output........................................................................................................................ 469
Set analogue output .................................................................................................................. 471
6005
For testing it might be useful to set the value of an output without being affected by the PLC program.
The device helps you.
WARNING
Risk of personal injury! Risk of material damage to the machine/plant!
After changing the slave outputs the output values remain unchanged.
The output values only change in the following cases:
Manual new setting of the outputs via Slave Setup,
when changing from projection mode to protected mode, unless the "slave reset" function was
deactivated via the menu,
host processes the outputs,
deactivate and restart the gateway.
►
Secure the concerned area.
►
Only trained personnel is allowed to set outputs manually.
►
Switch the outputs off again immediately after the end of the test!
Info
Password level 2 required:
chapter Password setting (
→
page
Changed values are not adopted in case of a wrong password level.
NOTE
Changes to the outputs are not effective in the following cases:
The corresponding outputs are processed by the host.
Changes of digital outputs on analogue modules.
Changes of analogue outputs on digital modules.
[MENU] > [Slave Setup] > Select master > Select slave