Troubleshooting
RTS errors – error codes R01...R43
494
16.7
RTS errors – error codes R01...R43
6040
RTS =
R
un
t
ime
S
ystem (= operating system of the device)
Menu operation interrupted.
Error message superposes the menu screen.
Error message only disappears after the following actions:
1. Error removed AND
2. Error message acknowledged with the right function key.
Error message
Cause(s)
Remedy
R01
Unknown RTS operating mode
The operating system does not recognise the set
operating mode of the device ("RUN" / "STOP" /
"GATEWAY").
Possible cause:
Modification of the device from a gateway variant
into a device with PLC support.
►
Switch the device off and keep the left
function key pressed during the switch-on
operation.
Master 1 MUX field error
During the transfer of the MUX fields from the
operating system the master detected an invalid
field number.
Possible causes:
1.
Parts of the operating system have been
overwritten by the PLC.
►
Check the cause for the wrong command
and correct.
►
Reinstall operating system.
R02
2.
Unacceptable interference on the 24 V
power supply.
►
Ground the device via the rail.
►
Connect the FE terminal to the machine
ground.
►
Use a switched-mode power supply to
supply the device with power.
►
Repeat
command.
R03
Master 2 MUX field error
R02
R04
Master 1 protocol error (EDET)
The master has detected a protocol error during
the transfer of the data fields.
R02
R05
Master 2 protocol error (EDET)
R02
R06
General RTS program failure
The operating system has detected an invalid
status in the process while executing the program
internally.
Possible cause:
Operating system software error.
►
Reinstall operating system.
R07
Projection mode not active
It was tried to execute an AS-i command which is
only permitted in the projection mode.
►
Switch master to the operating mode
"Projection mode":
How to switch the operating modes for
the AS-i master. (
→
)