Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Acyclic services for Profibus DPV1
Acyclic command in the DPV1 command channel
353
Response from device to fieldbus master in the normal case
Bit
Offset
Word no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
Command status (
→
page
) = 6F
hex
2
reserved = 0
reflected command number
3
reflected sub command
reflected slave address
4
LEDs OSSD 1
LEDs OSSD 2
data call 1
data call 0
5
OSSD2 not green
OSSD1 not green
6
1st colour output circuit 1
1st module address output circuit 1
7
2nd colour output circuit 1
2nd module address output circuit 1
8
3rd colour output circuit 1
3rd module address output circuit 1
9
4th colour output circuit 1
4th module address output circuit 1
10
5th colour output circuit 1
5th module address output circuit 1
11
6th colour output circuit 1
6th module address output circuit 1
12
1st colour output circuit 2
1st module address output circuit 2
13
2nd colour output circuit 2
2nd module address output circuit 2
14
3rd colour output circuit 2
3rd module address output circuit 2
15
4th colour output circuit 2
4th module address output circuit 2
16
5th colour output circuit 2
5th module address output circuit 2
17
6th colour output circuit 2
6th module address output circuit 2
18
field number = 0/1
reserved = 0
19
not changed *)
not changed *)
*)
IMPORTANT:
For the query read only the required bytes!
Unused bytes can contain information of previous queries.
Description of the different fields in word no. 4 for [LEDs OSSD 1/2]
Value [hex.]
Value [bin.]
Meaning
0
0000
green = contacts of the output circuits closed
1
0001
yellow = startup / restart disable active
2
0010
yellow flashing or red: = contacts of the output circuits open
3
0011
red flashing = error on the level of the monitored AS-i components
> 4
> 0100
reserved