Technical data
Operating voltage
10...30 V DC; SELV
Current consumption
200 mA (24 V DC)
(The current consumption in the case of an error
must be limited to 1 A by appropriate measures)
Function keys
12, to be evaluated via application program
Operating keys
4 arrow keys, to be evaluated via application program
Key labelling
3 exchangeable strips to be inserted
Status LEDs
12, freely configurable via application program
Rows of LEDs
2 x 10-digit, red/green, operating mode selectable
Interface
CAN Interface (ISO 11898)
Baud rate
20 Kbits/s...1 Mbits/s (default setting 125 Kbits/s)
Communication profile
CANopen, CiA DS301 V4.0
Device profile
manufacturer-specific
CAN
Full-CAN 2.0
Node ID (default)
hex 20 (= 32)
Operating temperature
-20...+85°C
Storage temperature
-30...+85°C
Protection
IP64 / III
Housing material
Noryl
Dimensions (W x H x D)
190 x 90 x 32 mm
Overall height for wall mounting
32 mm
height for control cabinet mounting
7 mm
depth for control cabinet mounting
25 mm
Maximum depth of the front panel
2.5 mm
Connection
5 WAGO cage-clamp terminals
Wiring
1: CAN_H, 2: CAN_L, 3: GND, 4: GND, 5: +24 V
Dimensions
CAN KEYPAD MODULE
CPM 100
PAGE
28
90
190
32