9 Parameter setting
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
Depending on the parameter setting, the parameters available in the menu may change.
Parameter setting process in general:
Intention
Action
Change from the operating to the parameter setting mode
[●] > 1 s
Change to the submenu
Press [▼] / [▲] to navigate to the submenu (e.g. “Display”),
then press [●] < 1 s.
Select the requested parameter
Press [▼] / [▲] to navigate to the parameter (e.g. “Value font
color”), then press [●] < 1 s.
Modify the parameter value
Select parameter value
Press [▼] / [▲] to navigate to the parameter value (e.g.
“Green”). Press [●] < 1 s to save the value.
Enter numerical value
Press [●] < 1 s to jump to the desired position.
Press [▼] / [▲] to change the value and press [●] > 1 s to
save it.
Enter text
Press [●] < 1 s to jump to the desired position.
Press [▼] / [▲] to change the value, long press [▼] / [▲] for
special and lower case letters.
Press [●] > 1 s to save all characters to the left of the select-
ed position. All other characters are removed.
Return to the next higher menu level
[esc]
OR
menu item [Back]
Return to the operating mode
> 30 seconds (timeout)
OR
press [esc] repeatedly.
OR
From the main menu: menu item [run]
9.1 Input type
The parameter [Input type] defines the type of input signal. The following settings are possible:
Value
Description
Volt/Ampere
Voltage/current measurement
Pt100(0)
Temperature measurement via Pt100 or Pt1000
Thermo
Temperature measurement via thermocouple
Frequency
Frequency measurement
RPM/Speed
Speed measurement
Count up / Count down
Counter
Tab. 1: Input type