Universal display
DX1063
27
Value
Description
Below limit
The alarm is activated when the switch point is not reached.
In window
The alarm is activated in the specified window.
Out of window
The alarm is activated outside the specified window.
Tab. 5: Ax mode
u
Select [Ax fault] and set which state the alarm displays in the event of an internal error of the unit:
Value
Description
No change
Retain current alarm
Off
No alarm
On
Alarm active
Tab. 6: Ax fault
u
Select [Ax output sel.] and set the relay to be switched with this alarm:
•
No relay
•
Relay 1
•
Relay 2
u
Select [Ax setpoint] and set the switch point for this alarm:
•
-1999…9999
The parameter [Ax setpoint] is only available in [Ax mode] [Exceed limit] and [Below limit]. It can
be combined with the parameter [Ax hysteresis].
u
Select [Ax hysteresis] and set the hysteresis for the switch point [Ax setpoint]:
•
0000…9999
The parameter [Ax hysteresis] is only available in [Ax mode] [Exceed limit] and [Below limit].
u
Select [Ax upper value] and set the upper limit for the window function:
•
-1999…9999
u
Select [Ax lower value] and set the lower limit for the window function:
•
-1999…9999
The parameters [Ax upper value] and [Ax lower value] are only available in [Ax mode] [In
window] and [Out of window].
u
Select [Ax reset delay] and set the switch-off delay for this alarm:
•
0…100 s
u
Select [Ax switching delay] and set the switch-on delay for this alarm:
•
0…100 s
The parameters [Ax reset delay] and [Ax switching delay] are only available in [Ax mode]
[Exceed limit], [Below limit], [In window] and [Out of window].
A delayed switch-off and switch-on of the alarm can be configured separately for the switch
points.
The internal time counter is not stored permanently and reset by a device start.
u
Select [Ax flashing] and set the flashing of the display for this alarm:
•
Continuous
•
Flashing