Universal display
DX1063
29
Value
Description
None
No indication of overflow or underflow. In these cases, the unit
continues to display the highest / lowest value.
ADC
[OL] is indicated if [Max. display value] is exceeded.
[UL] is indicated if [Min. display value] is not reached.
Full range
[OL] is indicated if [Analog end] is exceeded.
[UL] is indicated if [Analog start] is not reached.
(see
)
5 % range
[OL] is indicated if [Analog end] exceeds the set measuring
range by 5%.
[UL] is indicated if [Analog start] undercuts the set measuring
range by 5%.
Example:
Measuring range = [Analog end] - [Analog start] =
20 mA - 0 mA = 20 mA, of which 5% = 1 mA
(see
)
10 % range
[OL] is indicated if [Analog end] exceeds the set measuring
range by 10%.
[UL] is indicated if [Analog start] undercuts the set measuring
range by 10%.
Example:
Measuring range = [Analog end] - [Analog start] =
20 mA - 0 mA = 20 mA, of which 10% = 2 mA
(see
)
Tab. 7: Overrange
The parameter [Overrange] is only available with [Input type] [Volt/Ampere], [Frequency] and
[RPM/Speed].
With [Input range] [4…20 mA], underflow cannot be deactivated. With [Overrange] = [None] or
[ADC], the unit will always display an analogue input value < 1 mA as UL.
u
Select [Min. display value] and set the display value for underflow for current and voltage
measurements:
•
-1999…9999
The parameters [Min. display value] and [Max. display value] are only available with [Input type]
[Volt/Ampere] and with [Overrange] = [ADC].
With [Input range] [4…20 mA], the unit will already indicate an underflow at an input signal < 1
mA to indicate a sensor failure.
u
Select [Max. display value] and set the display value for overflow for current and voltage
measurements:
•
-1999…9999
The parameter [Max. display value] is only available with [Input type] [Volt/Ampere].
u
Select [Direction keys] and set the function for the keys [▲] and [▼]:
Value
Description
No function
No function of these keys in operating mode
Min/Max req.
In operating mode, the maximum value is indicated with [▲],
the minimum value with [▼].
Set limits
In operating mode, limit values are changed with [▲] and [▼].
Tab. 8: Direction keys
u
Select [esc key] and set the function for the [esc] key: