DX1063
Universal display
30
Value
Description
No function
No function of this key in operating mode
Taring
In operating mode, press [▲] to perform taring (offset).
Tab. 9: esc key
The parameter [esc key] is only available with [Input type] [Volt/Ampere], [Frequency] and
[RPM/Speed].
u
Select [Zero lock] and set the desired value for zero point steadying:
•
0…99
This forces the display to indicate a value of “0” for very small input values. With the input values
0...99, the last two digits of the 4-digit digital display can be steadied.
The parameter [Zero lock] is only available with [Input type] [Volt/Ampere], [Frequency] and
[RPM/Speed].
u
Select [Arithmetic] and configure the unit to indicate the measured value or a calculated value in
the display:
Value
Description
No
Indication of the measured value
Square root
Indication of the calculation value
Root(Measured value*Final value)
Square
Display of the calculation value
(Display value)
2
/Final value
Reciprocal
Indication of the calculation value
Final value/Measured value
Tab. 10: Arithmetic
The denominator of fractions should not be 0 because a division by 0 is not possible. It creates an
undefined state and the display indicates overflow.
The parameter [Arithmetic] is only available with [Input type] [Volt/Ampere], [Frequency] and
[RPM/Speed].
u
Select [User PIN] and set the 4-digit PIN code required to access the user menu:
•
0000…9999
User menu = restricted parameter setting mode
Administrator menu = full access to all parameters
Parameter setting options can be restricted via the user menu. The range of the user menu is
configured via the parameter [User level].
When leaving the parameter setting mode from the user menu, the user is asked whether the
user PIN should be activated (Lock) or not (Unlock).
If the user menu is exited with Unlock, the unit will open the user menu – or the administrator
menu, if this is also unlocked – without a PIN request the next time the user changes into
parameter setting mode.
u
Select [Administrator PIN] and set the 4-digit PIN code required to access the administrator menu:
•
0000…9999
The administrator menu contains all parameter setting options.
When leaving the parameter setting mode from the administrator menu, the user is asked
whether the user PIN should be activated (Lock) or not (Unlock).
If the administrator menu is exited with Unlock, the unit will open the administrator menu without
a PIN request the next time the user changes into parameter setting mode.
u