DX1063
Universal display
26
•
2 Hz
•
5 Hz
•
10 Hz
•
20 Hz
•
50 Hz
•
100 Hz
•
200 Hz
•
500 Hz
•
No
u
Select [End value] and set the value to be displayed after reaching the final value of the measuring
range:
•
-1999…9999
u
Select [End count] and set the count at which the [End value] value is displayed:
•
0001…9999
u
Select [Reset] and set the value to be set by a reset:
•
0000…9999
If [Reset] = 0, a reset will set the count to the start value.
If [Reset] = 1...9999, the count will be reduced by the set value with [Input type] [Count up], or
increased by the set value with [Input type] [Count down].
u
Select [Decimal point] and set the position of the decimal point in the display:
•
cccc
•
ccc.c
•
cc.cc
•
c.ccc
u
Select [Scale unit] and enter the unit of the measured value.
A maximum of 7 characters is possible.
To enter the characters via the unit keys:
see
9.2 Alarms
Alarms are configured under [Alarms]. A maximum of 8 alarms can be configured (A1…A8). As the
configuration options for the 8 alarms are identical, the alarm is called Ax here.
If several alarms are present at the same time, the alarm with the highest number is displayed and the
corresponding configuration is used.
Parameter setting:
ü
The alarm Ax is selected.
u
Select [Ax mode] and set when this alarm should be active:
Value
Description
Off
The alarm is off.
No other parameters are displayed for this alarm.
On
The alarm is activated in operating mode.
Exceed limit
The alarm is activated when the switch point is exceeded.