DX1063
Universal display
20
9.1.1 Volt/Ampere
The unit displays the measured voltage or current value.
In addition, it is possible to calibrate the unit via the connected measuring section.
Carry out a calibration (optional):
ü
[Input type] [Volt/Ampere] is selected.
u
Select [Input range] and set the desired measuring range:
•
Sens V (0...10 V input)
•
Sens mA (0…20 mA input)
u
Select [End value] or [Start value].
u
Enter the measured value to be displayed at the current input value (analogue value).
u
Confirm [Sens.Calib] with [Yes] to start the calibration and accept the current analogue input value
as [Analog start] or [Analog end].
OR
cancel [Sens.Calib] with [no] to use the set [Analog start] or [Analog end] value without any
changes.
Calibration makes it possible to assign the current analogue input value as an [Analog start] or
[Analog end] value to the set [Start value] or [End value].
Example: A distance sensor (4...20 mA) is to determine the drilling depth. Max. drilling depth: 80
mm
ü
[Input type] [Volt/Ampere] is selected.
u
Bring the drill to the surface of the workpiece (0 mm drilling depth).
u
Select [Input range] [Sens mA].
u
Select [Start value].
u
Enter 0 as [Start value].
u
Confirm [Sens.Calib] with [Yes].
w
The unit assigns the display value 0 to the analogue input value.
u
Move the tool 80 mm further (80 mm drilling depth).
u
Select [Sens.Calib].
u
Select [End value].
u
Enter 80 as [End value].
u
Confirm [Sens.Calib] with [Yes].
w
The unit assigns the display value 80 to the analogue input value.
w
In the operating mode, the unit calculates the drilling depth from the analogue input value
and displays it in mm.
Parameter setting:
ü
[Input type] [Volt/Ampere] is selected.
u
Select [Input range] and set the desired measuring range:
•
0…10 V
•
0…2 V
•
0…1 V
•
0...50 mV
•
0...20 mA
•
4...20 mA