Universal display
DX1063
23
Parameter setting:
ü
[Input type] [Frequency] is selected.
u
Select [Input signal] and set the type of input signal:
•
TTL
•
NPN
•
PNP
•
NAMUR
u
Select [Input range] and set the frequency range:
Value
Description
9.999 Hz
0.000…9.999 Hz
99.99 Hz
0.00…99.99 Hz
999.9 Hz
0.0…999.9 Hz
9999 Hz
0…9999 Hz
Tab. 3: Input range
u
Select [Filter] and set the desired input filter to avoid interference signals:
•
2 Hz
•
5 Hz
•
10 Hz
•
20 Hz
•
50 Hz
•
100 Hz
•
200 Hz
•
500 Hz
•
No
u
Select [End value] and set the value to be displayed at the input frequency [Frequency end]:
•
-1999…9999
u
Select [Start value] and set the value to be displayed at the input frequency [Frequency start]:
•
-1999…9999
u
Select [Decimal point] and set the position of the decimal point in the display:
•
cccc
•
ccc.c
•
cc.cc
•
c.ccc
u
Select [Scale unit] and enter the unit of the measured value.
A maximum of 7 characters is possible.
To enter the characters via the unit keys:
see
u
Select [Frequency end] and enter the analogue input value at which the [End value] is to be
displayed:
•
0000…9999 Hz
u
Select [Frequency start] and enter the analogue input value at which the [Start value] is to be
displayed:
•
0000…9999 Hz