Universal display
DX1063
21
u
Select [End value] and set the value displayed at the analogue input value [Analog end]. [Analog
end] is the final value of the measuring range by default, but it can be adjusted.
•
-1999…9999
u
Select [Start value] and set the value displayed at the analogue input value [Analog start]. This is
the initial value of the measuring range by default, but it can be adjusted.
•
-1999…9999
u
Select [Decimal point] and set the position of the decimal point in the display:
•
cccc
•
ccc.c
•
cc.cc
•
c.ccc
u
Select [Scale unit] and enter the unit of the measured value.
A maximum of 7 characters is possible.
To enter the characters via the unit keys:
see
u
Select [Analog end] and enter the analogue input value at which the [End value] is to be displayed:
•
-19.99…99.99 V / mV / mA
u
Select [Analog start] and enter the analogue input value at which the [Start value] is to be
displayed:
•
-19.99…99.99 V / mV / mA
End value
displayed value
Start value
Analog
end
Analog
start
analog input value
[V / mV / mA]
Fig. 45: Application [Analog start] / [Analog end]
u
Optionally select [Value offset] and set the value for the display offset:
•
-1999…9999
u
Select [Linearization points] and set the desired number of linearization points:
•
0…9
For the number of linearization points configured under [Linearization points], configure [Display
P#x(Y)] and [Analog P#x(X)] respectively:
u
Select [Display P#x(Y)] and set the display value for the corresponding analogue value of the
relevant linearization point:
•
-1999…9999
u
Select [Analog P#x(X)] and set the analogue value for the corresponding display value of the
relevant linearization point:
•
-19.99…99.99 V / mV / mA