Step 1: Calculate typical response times
43023
► Calculate typical response times of the safety functions of the device:
Without safe cross communication
AS-i output
Local output
FSoE slave output
AS-i input
30 ms +
2*T(SafetyTask) +
15 ms
30 ms +
2*T(SafetyTask) +
8 ms
30 ms +
2*T(SafetyTask) +
4*T(MainTask) +
4*T(MapTask) + 32 ms
Local input
16 ms +
2*T(SafetyTask) +
15 ms
16 ms +
2*T(SafetyTask) +
8 ms
16 ms +
2*T(SafetyTask) +
4*T(MainTask) +
4*T(MapTask) + 32 ms
FSoE Slave
Eingang
32 ms +
4*T(MainTask) +
4*T(MapTask) +
2*T(SafetyTask) +
15 ms
32 ms +
4*T(MainTask) +
4*T(MapTask) +
2*T(SafetyTask) +
8 ms
32 ms +
4*T(MainTask) +
4*T(MapTask) +
2*T(SafetyTask) +
4*T(MainTask) +
4*T(MapTask) + 32 ms
With safe cross communication (Safety NetVars)
To device 2
From device 1
AS-i output
Local output
FSoE slave output
AS-i input
30 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
15 ms
30 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
8 ms
30 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms
Lokaler
Eingang
16 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
15 ms
16 ms
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
8 ms
16 ms
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms
FSoE Slave
Eingang
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
15 ms
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
8 ms
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
2*T(SafetyTask_Dev1) +
4*T(MapTask_Dev1) +
4*T(MainTask_Dev1) + 32 ms +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms +
2*T(SafetyTask_Dev2) +
4*T(MapTask_Dev2) +
4*T(MainTask_Dev2) + 32 ms
The formula in the table determine only the typical response time of the device. For the
calculation of the typical process response time the delay times of the safety AS-i
sensors/actuators and the respective input/output devices have to be added additionally
(T(sensor) + T(input) and T(output) + T(aktuator)).