SmartPLC SafeLine AC4S with fieldbus interfaces
39
>
6.4.3
Create test signal at local output
43244
Certain device types require an input signal as test pulse to detect a cross fault of the two input
channels. By means of the logical device SF_OUT_local_testpulse the programmer can create a test
signal at a local output.
To create a test signal at a local output:
►
Add logical device "SF_OUT_loal_testpulse" to the project tree
(→
Add logical device to the project tree
The parameters of the test pulse are firmly set; there are no additional configuration options
(
→
SF_OUT_local_testpulse
(
>
6.4.4
Remove safe local device from project
43061
To completely remove a safe device added to the local I/O interface the 2 instances of the logical
device must be deleted separately from the project tree.
1 Remove logical device from the standard area
►
Mark logical device in standard area of device tree.
►
Select [Edit] > [Delete].
>
CODESYS removes the logical device from the standard area.
2 Remove logical device from the safety area
►
Mark logical device in the safety extension area of the device tree.
►
Select [Edit] > [Delete].
>
CODESYS removes the logical device from the safety extension area.