SmartPLC SafeLine AC4S with fieldbus interfaces
21
>
5.5.2
Set communication path of the fail-safe PLC
43038
To configure the connection between CODESYS programming software and the fail-safe PLC of
AC4S:
Requirements:
>
Communication path to Standard PLC is correctly set (→
Set communication path of Standard-SPS
1 Select communication settings
►
In the project tree: Double click on the [SamrtPLC_Safety_Extension] symbol
>
The editor window shows the tab [Communication Settings].
2 Set communication path
►
Activate [Scan Network...]
>
Window [Select Device] appears.
►
Mark node [Gateway-1] and start scan process with [Scan network].
>
Device scans network for devices.
>
Window shows detected devices and network path.
►
Select the sub-node of the SafeLine node in the network path.
>
Information field shows detailed information about selected node.
►
Click on [OK] to set the communication path to the fail-safe PLC.
3 Acknowledge connection to the fail-safe PLC
>
Window [Connection to the Fail-safe PLC] appears.
►
Enter the serial number of the device in the field [Instance identification].
►
Click on [OK] to acknowledge the input.
>
CODESYS verifies the connection to the fail-safe PLC.
>
CODESYS can log in to the fail-safe PLC.