SmartPLC SafeLine AC4S with fieldbus interfaces
107
>
Switch operating states
42549
To switch between the operating states of the standard application choose one of the following
options:
>
Start Standard PLC application
42572
To start a Standard PLC application stored on the device:
CODESYS:
►
In the standard area of device tree: highlight standard application as active application.
►
Use [Online] > [Login] to establish the connection with the CODESYS Standard PLC.
►
Use [Debug] > [Start] to start the processing of the active application.
>
Application goes to RUN state.
►
Optional: repeat process for additional applications.
GUI / web interface:
►
>
>
►
Select the [Applications] tab.
►
Use [
] / [
] to select the required application.
>
Page shows the operating status of the selected application.
►
Press [Start] function key to start the processing of the selected application.
>
Application goes to RUN state.
►
Optional: repeat process for additional applications.
>
Stop Standard PLC application
42570
To stop a Standard PLC application stored on the device:
CODESYS:
►
In the standard area of device tree: highlight standard application as active application.
►
Use [Online] > [Login] to establish the connection with the CODESYS Standard PLC.
►
Use [Debug] > [Stop] to stop the processing of the active application.
>
Application goes to STOP state.
►
Optional: repeat process for additional applications.
GUI / web interface:
►
>
>
►
Select [Applications] tab.
►
Use [
] / [
] to select the required application.
>
Page shows the operating status of the selected application.
►
Press [Stop] function key to stop the processing of the selected application.
>
Application goes to STOP state.
►
Optional: repeat process for additional applications.