Applications
8-28
IDEC SmartRelay User’s Manual
8.6.3
Rainwater Pump with FL1A-H10RCB
Apart from IDEC SmartRelay, you only need the pressure
switch and the float switches to control the pump. If you are
using a 3–phase AC motor, you must use a master
contactor for switching the pump. On systems using
single–phase AC pumps, you must fit a contactor if the AC
pump requires a higher current than can be switched by
the output relay Q1. The power of a solenoid valve is so
low that it can normally be controlled directly.
•
K1
Master contactor
•
Y1
Solenoid valve
•
S1
(NO contact)
Pressure switch
•
S2
(NO contact)
Float switch
•
S3
(NC contact)
Float switch
•
S4
(NC contact)
Float switch
L1
N
I1
I2
I3
I4
I5
I
Q1
Q2
Q3
Q
Idec SmartRelay
K1
Y1
Pump
S4
S3
L1
N
S
S2
p<
Mains water inlet