![IDEC SmartRelay FL1A-H12RCE Manual Download Page 96](http://html1.mh-extra.com/html/idec/smartrelay-fl1a-h12rce/smartrelay-fl1a-h12rce_manual_3719442096.webp)
IDEC SmartRelay Functions
4-28
IDEC SmartRelay User’s Manual
4.4.6
Current Impulse Relay
Brief description
The output is set and reset by a short pulse at the input.
Symbol in
IDEC
SmartRelay
Connection
Description
Input Trg
Use the Trg input (trigger) to
switch the output Q on and
off.
Input R
The input R resets the
current impulse relay and
sets the output to 0.
Parameter Par
This parameter is used to
switch retentivity on or off.
Rem:
off = no retentive feature
on = the state can be stored
retentively
Output Q
Q switches on when Trg is
sent and remains switched
on until T expires.
Timing diagram
Description of function
Every time the state at the input Trg changes from 0 to 1,
the output Q changes its state, i.e. the output switches on
or off.
Use the R input to reset the current impulse relay to its
initial state (i.e. the output is set to 0).
After power failure the current impulse relay is reset. The Q
output changes to 0 if the retentive feature is not on.
Trg
Q
R
The bold part of the timing
diagram appears in the current
impulse relay symbol.
Summary of Contents for SmartRelay FL1A-H12RCE
Page 1: ...IDEC SmartRelay Manual March 2001 www idec com ...
Page 16: ...Getting to Know IDEC SmartRelay 1 6 IDEC SmartRelay User s Manual ...
Page 32: ...Installing and Wiring IDEC SmartRelay 2 16 IDEC SmartRelay User s Manual ...
Page 132: ...IDEC SmartRelay Functions 4 64 IDEC SmartRelay User s Manual ...
Page 184: ...Applications 8 32 IDEC SmartRelay User s Manual ...
Page 204: ...IDEC SmartRelay Menu Structure E 2 IDEC SmartRelay User s Manual ...
Page 206: ...Type Numbers F 2 IDEC SmartRelay User s Manual ...
Page 208: ...Abbreviations G 2 IDEC SmartRelay User s Manual ...