Technical Specifications
A-4
IDEC SmartRelay User’s Manual
FL1A-H10RCB
FL1A-B10RCB
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
In groups of
1
Activation of digital input
Yes
Continuous current I
th
(per
connector)
Max. 10 A
Incandescent lamp load
(25,000 switching cycles) at
230/240 V AC
115/120 V AC
1000 W
500 W
Fluorescent tubes with electr.
control gear (25,000 switching
cycles)
10 x 58 W (at 230/240 V AC)
Fluorescent tubes,
conventionally compensated
(25,000 switching cycles)
1 x 58 W (at 230/240 V AC)
Fluorescent tubes,
uncompensated (25,000
switching cycles)
10 x 58 W (at 230/240 V AC)
Short circuit-proof cos 1
Power protection B16
600A
Short-circuit proof cos 0.5 to
0.7
Power protection B16
900A
Parallel switching of outputs to
increase power
Not permitted
Protection of output relay (if
desired)
Max. 16 A,
characteristic B16
Switching rate
Mechanical
10 Hz
Ohmic load/lamp load
2 Hz
Inductive load
0.5 Hz
Minimum Switching Load
500mA, 12V
Summary of Contents for SmartRelay FL1A-H12RCE
Page 1: ...IDEC SmartRelay Manual March 2001 www idec com ...
Page 16: ...Getting to Know IDEC SmartRelay 1 6 IDEC SmartRelay User s Manual ...
Page 32: ...Installing and Wiring IDEC SmartRelay 2 16 IDEC SmartRelay User s Manual ...
Page 132: ...IDEC SmartRelay Functions 4 64 IDEC SmartRelay User s Manual ...
Page 184: ...Applications 8 32 IDEC SmartRelay User s Manual ...
Page 204: ...IDEC SmartRelay Menu Structure E 2 IDEC SmartRelay User s Manual ...
Page 206: ...Type Numbers F 2 IDEC SmartRelay User s Manual ...
Page 208: ...Abbreviations G 2 IDEC SmartRelay User s Manual ...