EVO S -
Installation and Servicing
Diagram: VF11
page 5 / 9
Line No. Value
Adjust the clock rate
Clock mode
(6640)
Master
•
Heating circuit 1 / 2
menu
Adjust the comfort setting
Comfort setpoint
(710/1010) - - -
Adjust the curve slope
Heating curve slope
(720/1020) - - -
•
Switch the heating regime to permanent comfort
•
Domestic hot water
menu
Adjust the comfort setting
Nominal setpoint
(1610) - - -
• Activate the DHW mode
• Configuration
menu
Save the sensors
Save sensors
(6200)
Yes (switches back
to no automatically)
On boiler n°2 or the following boilers: slave
• Configuration
menu
Boiler pump supplied by IDEAL
No adjustments necessary
Boiler pump supplied by the customer
(all-or-nothing control)
Relay output QX3
(5892) Boiler pump Q1
Start the third heating circuit
Heating circuit 1
(5710)
On
Start the fourth heating circuit
Heating circuit 2
(5715)
On
Configure the alarm output
Relay output QX1
(5890)
Alarm output K10
Configure the extension modules
Function extension module 1
(6020)
Heat circuit 1
Function extension module 2
(6021)
Heat circuit 2
•
Configure as a slave of the cascade:
LPB network
menu
Appliance number
Device address
(6600)
2 (or following, for
the other slaves)