background image

12 / 136  

00RNO0333-B (U0625869)

EVO S  -  

Installation and Servicing

EVO S

50

70

95

115

135

A

(mm)

541

B

(mm)

477

574

692

800

C

(mm)

890

D

(mm)

408

E

(mm)

66,5

F

(mm)

12,3

G

(mm)

103,5

H

(mm)

85,5

I

(mm)

86

J

(mm)

133

L

(mm)

190

M

(mm)

95

N

(mm)

241

242,5

O

(mm)

143,5

120

P

(mm)

86

111

Ø Q

Heating return connection

G 1"1/4

Ø R

Gas supply

G 1"

Ø S

Heating outlet connection

G 1"1/4

Ø T

Safety valve connection

G 1/2" (female)

Ø U

Condensate evacuation

(mm)

24

Ø V

Air inlet

(mm)

125

150

Ø W

Fume duct

(mm)

80

100

X

Valve angle

16°

Y

(mm)

45

Summary of Contents for EVO S 50

Page 1: ...nd performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cation and maintenanc...

Page 2: ......

Page 3: ...L SPECIFICATIONS 11 3 1 Dimensions 11 3 2 Boiler components 13 3 3 Combustion at 15 C and 1013 mbar 16 3 4 Conditions of use 18 3 5 Electrical connection 18 4 INSTALLATION 19 4 1 Installing the boiler...

Page 4: ...AULIC DIAGRAMS AND CONFIGURATIONS 42 9 1 Selection diagrams 42 9 2 Symbols used in the diagrams 43 9 3 List of diagrams 43 9 4 Specific configurations when connecting to 0 10V outputs Ux 104 10 SPARE...

Page 5: ...nts WARNING Not following these instructions may lead to damage when installing or to other objects DANGER Not following these instructions may cause injuries and serious material damage DANGER Not fo...

Page 6: ...of life DANGER It is forbidden to use water containing glycol 1 5 1 Preparation of the water circuit before commissioning the boiler For all installation work new or renovation the water network pipes...

Page 7: ...erating at a low power with high primary water flow When the tap water lacks the desired qualities e g high level of hardness water treatment is required The fill water must be treated and whenever ne...

Page 8: ...ecommended in order to ensure that the unit will last In most cases this consists of adding corrosion inhibitors in the form of chemical solutions to the unit It is recommended to contact water treatm...

Page 9: ...of less than or equal to 70 kW is available in appendix A Eco design 2009 125 EC In application of the directive and according to the requirements of the EU regulation No 813 2013 of 02 August 2013 th...

Page 10: ...essures given below should be measured at the input to the gas valve H G20 natural gas G31 propane Nominal pressure mbar 20 37 Minimum pressure mbar 17 25 Maximum pressure mbar 25 45 10 136 00RNO0333...

Page 11: ...27 08 2018 11 136 EVO S Installation and Servicing figure 1 Dimensional characteristics 3 TECHNICAL SPECIFICATIONS 3 1 Dimensions U0561520...

Page 12: ...6 5 F mm 12 3 G mm 103 5 H mm 85 5 I mm 86 J mm 133 L mm 190 M mm 95 N mm 241 242 5 O mm 143 5 120 P mm 86 111 Q Heating return connection G 1 1 4 R Gas supply G 1 S Heating outlet connection G 1 1 4...

Page 13: ...Ignition transformer 6 Fume temperature sensor 7 Bleed valve 8 Water return temperature sensor 9 Flowmeter 10 Water outlet temperature sensor 11 Pressure sensor 12 Anti return flap 13 Condensate siph...

Page 14: ...erature sensor 9 Flowmeter 10 Water outlet temperature sensor 11 Pressure sensor 12 Anti return flap 13 Condensate siphon supplied unmounted 14 User interface control panel 15 NAVISTEM B3000 unit 16 A...

Page 15: ...6 Fume temperature sensor 7 Bleed valve 8 Water return temperature sensor 9 Flowmeter 10 Water outlet temperature sensor 11 Pressure sensor 12 Anti return flap 13 Condensate siphon supplied unmounted...

Page 16: ...zle pressure B23P 50 30 C Qn Qall Qmin Pa Combustion air flow rate at Qn m3 h NOx class Flue gas removal and air inlet type classifications EVO S 50 70 95 115 135 56 4 69 9 95 7 119 5 134 0 61 0 76 8...

Page 17: ...Qn Qall Qmin C Inside diameter of flue gas output mm Maximum allowable nozzle pressure B23P 80 60 C Qn Qall Qmin Pa Maximum allowable nozzle pressure B23P 50 30 C Qn Qall Qmin Pa Combustion air flow...

Page 18: ...n with accessories W Electrical power consumption in standby mode W Max length of sensor cables m Power terminal output V A Maximum start setting temperature C Safety temperature C Maximum service pre...

Page 19: ...iagram opposite and table below These values cannot be substituted for the specific regulatory requirements B23 B23P C13 C33 S 50 S 70 to S 135 S 50 S 70 to S 135 S 50 S 70 to S 135 80 125 110 125 160...

Page 20: ...es of the art that apply in the country where the boiler will be installed The exhaust extraction ducts must be made in a material resistant to the condensate that can form when the boiler is operatin...

Page 21: ...the boiler to a B23 chimney duct This kit is suitable for 160 external ducts IMPORTANT Under no circumstances is use of these mandatory accessories a substitute for checking the dimensioning of the ch...

Page 22: ...e use of the Chimney Adaptor accessory is mandatory to connect a VARFREE boiler to a B23 chimney duct The table below represents the accessories available for each boiler type IMPORTANT Check that the...

Page 23: ...s incorporated in the boiler To do this use a minimum slope of 3 towards the boiler in the horizontal parts To ease fitting coat the joints with liquid soap or an appropriate grease IMPORTANT If sever...

Page 24: ...AVISTEM B3000 boiler command table instructions If necessary press the ESC button to return to the main screen Open the Burner control menu Adjust the ignition speed parameter 9512 Connection type 951...

Page 25: ...ding the terminal for the type C33 In addition in calculating the duct length take the following equivalences into account 90 elbow 1 m of straight duct 45 elbow 0 5 m of straight duct Use a minimum s...

Page 26: ...eck whether the boiler uses G20 or G31 gas If it uses G31 make the changes described in chapter 4 5 The gas line must not be subject to any mechanical stress risk of loss of gas tightness of the gas v...

Page 27: ...switch off the electric power supply Disconnect the electric cable and connect on the gas valve Undo the two nuts before and after the valve see figure below and remove the valve from the boiler Undo...

Page 28: ...2750 2550 2550 6250 figure 11 EVO S 50 settings 4 5 3 Adjustment of the gas valve Before starting the burner on the gas valve preset the gas flow rate using the gas flow rate adjustment screw R1 to t...

Page 29: ...31 label provided in place of the original label G20 Door open pre setting Checking the door closed settings Model Gas Pre adjustment of the gas flow adjusting screw R1 CO2 Pmax Indicative CO2 Pmin CO...

Page 30: ...13 Pressure drop Hydraulic pressure drop mbar Hydraulic pressure drop mCE Flow rate m3 h S 5 0 S 7 0 S 9 5 S 1 1 5 The boilers are equipped with the following elements an anti return flap a manual dr...

Page 31: ...must be a maximum of 4 bar when hot and a minimum of 1 bar when cold Check that the boiler and its installation are completely bled check the boiler levelling with a spirit level Condensate removal Re...

Page 32: ...ce is strongly advised Please refer to the installation and user manuals of the NAVISTEM B3000 boiler controller for more information about the electrical connections on the control panel characterist...

Page 33: ...or Input prog client 0 10V Alarm relay Input prog client contact Pompe modulante View from inside the control panel Front of the boiler Rear of the boiler 1 packing gland and 2 slots for signal connec...

Page 34: ...IHM X11 X50 X24 AGU 2 550 OCI 345 NAVISTEM B3000 00RET0069 C U0556984 C B2 B7 35 120 150 VF 35 120 150 VF 1 2 1 2 7 6 5 4 3 2 1 7 6 5 4 3 2 1 3 1 1 3 1 2 3 1 2 3 4 U BX22 M BX21 M H2 U BX22 M BX21 M...

Page 35: ...is active when a request for heat is in progress on the boiler If the circulation pump does not have a control switch Directly wire the power supply of the circulation pump 230 VAC 1A max to the term...

Page 36: ...a EVO S boiler to a B23 or B23P chimney duct 5 2 First use Before packing all boilers are subjected to a factory test using group H type G20 natural gas during which all the settings are done For fir...

Page 37: ...eck that the gas pipe diameter is correctly sized It is necessary to stop all the boilers together abruptly using the boiler room main circuit breaker to check that the gas pressure regulator safety d...

Page 38: ...ometry of the ignition electrode gap width and the ionising electrode If necessary replace the electrodes Condensate removal siphon Clean the removal siphon and check that the condensates flow correct...

Page 39: ...turi assembly and carefully put it in a clean place If there are any deposits in the combustion chamber brush the tubes of the exchanger with a non metal brush Chemical cleaning of the combustion cham...

Page 40: ...50 models six nuts on S 70 to S 135 models Maximum tightening torque 5 Nm Connect the gas supply Check that the gas circuit is sealed with a foaming product Install the control panel Switch on the ele...

Page 41: ...ks a For the disposal of the product and the component parts the services of an accredited waste disposal company should be used b For more information on waste disposal management contact the Local A...

Page 42: ...136 00RNO0333 B U0625869 EVO S Installation and Servicing 9 HYDRAULIC DIAGRAMS AND CONFIGURATIONS 9 1 Selection diagrams page 46 page 48 page 54 page 88 page 95 page 69 page 74 pages 79 and 84 page 6...

Page 43: ...etworks 0 10V or LPB 44 VF1 Control 1 direct circuit with low limit and production of DWH 48 VF2 2 regulated circuits 1 direct circuit with low limit and production of DWH 54 VF3 4 regulated circuits...

Page 44: ...kit for LPB bus for dialogue over LPB bus 1 OCI 345 219285 The existing regulation system controls the installation s heating circuit It sends the outlet temperature set point to the boiler either ov...

Page 45: ...NECTION L2 N L3 N L3 L1 N QX2 QX3 QX1 BX2 Gnd BX3 Gnd B3 Gnd B9 Gnd H1 Gnd H5 Gnd Diagram VF1 page 2 4 L N PWM GND Boiler pump if supplied by IDEAL 230 VAC 50 Hz power supply 0 to 10V analogue input t...

Page 46: ...ion menu Configure the H1 input Function input H1 5950 Consumer request VK1 10V Voltage value 1 H1 5953 0 0 Function value 1 H1 5954 0 Voltage value 2 H1 5955 10 0 Function value 2 H1 5956 1000 for eq...

Page 47: ...t 7700 Relay output QX3 Reset the outputs Relay test 7700 No test Configuration menu Check the hydraulic diagram Check no heat source 1 6212 14 Check no heat source 2 6213 0 Check no storage tank 6215...

Page 48: ...t 1 QAZ 36 219481 Boiler pump supplied by the customer all or nothing control Extension module kit delivered with a network sensor QAD 36 1 AGU 2 550 219483 The boiler operates in variable flow temper...

Page 49: ...2 page 2 6 C RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135 219463 219464 219465 219466 AGU 2 550 230 VAC 50 Hz p...

Page 50: ...connections Start up the boiler only Carry out the adjustments below Line No Value Time and date menu Set the time Hours minutes 1 HH MM Set the date Day month 2 DD MM Set the year Year 3 YYYY Config...

Page 51: ...t according to the lower limit Switch the heating regime to permanent comfort Domestic hot water menu Adjust the comfort setting Nominal setpoint 1610 Activate the DHW mode Configuration menu Save the...

Page 52: ...Heating circuit 1 timer programme menu Preselection Preselection 500 Adjust the timer programming On off phases 501 506 Heating circuit 1 holiday menu Preselection Preselection 641 Adjust the timer pr...

Page 53: ...1646 Maintenance optimisation A maintenance message may be generated that does not set the boiler to fault This maintenance message may be displayed after the following 3 counters have expired Time si...

Page 54: ...QAZ 36 219481 Output sensor kit 1 QAC 34 219479 Room sensor kit 1 QAA 75 040954 The water law of the heating circuit is programmed on the NAVISTEM B3000 with a weekly heating programme The AGU 2 550...

Page 55: ...RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135 219463 219464 219465 219466 230 VAC 50 Hz power supply External s...

Page 56: ...year Year 3 YYYY Configuration menu Start up heating circuit 1 Heating circuit 1 5710 On Start up heating circuit 2 Heating circuit 2 5715 On Start up heating circuit 3 Heating circuit 3 5721 On IMPO...

Page 57: ...the extension modules Function extension module 1 6020 Heat circuit 2 Function extension module 2 6021 Heat circuit 3 Heating circuit 1 2 3 menu For each circuit Adjust the Comfort setpoint Comfort se...

Page 58: ...closure Relay test 7700 Relay output QX22 module 1 Heating circuit 2 pump Relay test 7700 Relay output QX23 module 1 Heating circuit 3 3 channel valve opening Relay test 7700 Relay output QX21 module...

Page 59: ...automatic comfort reduced switch according to the difference between the set point and the outdoor temperature see NAVISTEM B3000 manual Function not activated by default 24 hour heating limit 1032 1...

Page 60: ...burner parameter 7040 Number of starts parameter 7042 These last 2 parameters are dependent on the boiler s hydraulic installation We recommend using at least parameter 7044 for annual maintenance H C...

Page 61: ...y the RVS 63 integrated into an outside case at the boiler The boiler operates in variable flow temperature according to the outdoor temperature measured by the exterior sensor QAC 34 without a low te...

Page 62: ...DEAL AGU 2 550 n 1 AGU 2 550 n 2 Diagram VF4 page 2 8 C RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135 219463 219...

Page 63: ...ing valve Heating circuit No 2 Y5 Y6 Heating circuit No 2 circulator Q6 AGU 2 550 n 2 on Bo tier r gulateur RVS 63 B3 h M B9 k M H1 n M B1 p M BX1 n M BX2 n M B12 p M H3 n M BX3 n M BX4 n M UX n M QX4...

Page 64: ...0 Alarm output K10 Configure DHW pump Relay output QX2 5891 DHW ctrl elem Q3 If the boiler pump is supplied by customer Relay output QX3 5892 Boiler pump Q1 Configure the extension modules Function ex...

Page 65: ...uit 1 5710 On Start heating circuit 2 Heating circuit 1 5715 On Save the sensors Save sensors 6200 Yes switches back to no automatically LPB network menu Device number Device address 6600 1 Segment nu...

Page 66: ...ump Relay test 7700 Relay output QX23 module 1 HC2 3 channel valve opening Relay test 7700 Relay output QX21 module 2 HC2 3 channel valve close Relay test 7700 Relay output QX22 module 2 HC2 pump Rela...

Page 67: ...Reset the outputs Relay test 7700 No test Check the sensor values Circuit 3 network flow sensor B1 Flow temp B1 7732 en C Circuit 4 network flow sensor B12 Flow temp B12 7734 en C Diagram VF4 page 7 8...

Page 68: ...hours of the burner parameter 7040 Number of starts parameter 7042 These last 2 parameters are dependent on the boiler s hydraulic installation We recommend using at least parameter 7044 for annual ma...

Page 69: ...ature limit and with a weekly programme The flow rate of the heating pump in m3 h is adjusted to the real needs of the installation and as a minimum to P 25 with P power in th h of the boiler If the h...

Page 70: ...ture according to the outdoor temperature measured by the exterior sensor QAC 34 The heating water law is programmed on the NAVISTEM B3000 with or without a low temperature limit and with a weekly pro...

Page 71: ...nd H1 Gnd H5 Gnd C RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135 219463 219464 219465 219466 230 VAC 50 Hz power...

Page 72: ...n Configure the alarm output Relay output QX1 5890 Alarm output K10 Configure the direct circuit pump Q2 Relay output QX2 5891 Heat circuit pump HC1 Q2 Heating circuit 1 menu For each circuit Adjust t...

Page 73: ...hases 501 506 Heating circuit 1 holiday menu Preselection Preselection 641 Adjust the timer programming On off phases 642 643 Switch the heating regime to automatic Auto Maintenance optimisation A mai...

Page 74: ...e flow temperature required to produce the domestic hot water The flow rate of the pump in m3 h is adjusted to the real needs of the installation and as a minimum to P 25 with P power in th h of the b...

Page 75: ...X2 Gnd BX3 Gnd B3 Gnd B9 Gnd H1 Gnd H5 Gnd Diagram VF22 page 2 5 C RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135...

Page 76: ...VK1 Position a shunt on H1 OU reverse the contact direction Contact type 5951 Normally closed contact NC For the DHW to be effective an activator must be defined even if it is not connected Relay outp...

Page 77: ...t temperature of the boiler is then the set point of the DHW 56 C over value 13 C 69 C The DHW cycle stops when the sensor inside the tank reaches the DHW set point temperature 56 C The boiler then re...

Page 78: ...message may be generated that does not set the boiler to fault This maintenance message may be displayed after the following 3 counters have expired Time since last maintenance or commissioning set p...

Page 79: ...pump in m3 h is adjusted to the real needs of the installation and as a minimum to P 25 with P power in th h of the boiler The pump heating will have to allow to work in constant speed to insure the m...

Page 80: ...LECTRICAL CONNECTION BX2 Gnd BX3 Gnd B3 Gnd B9 Gnd H1 Gnd H5 Gnd C RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135...

Page 81: ...e output setting to be taken into account if the Consumer circuit is requested Flow temp setp cons request 1859 60 C depends on the Rubis setting Remove pump stoppage on DHW priority OEM setting DHW p...

Page 82: ...hydraulic diagram Check no heat source 1 6212 13 Check no heat source 2 6213 0 Check no storage tank 6215 4 Check no heating circuits 6217 0 Diagram VF23 page 4 5 Process description The consuming cir...

Page 83: ...r to fault This maintenance message may be displayed after the following 3 counters have expired Time since last maintenance or commissioning set parameter 7044 to 12 months Operating hours of the bur...

Page 84: ...The flow rate of the pump in m3 h is adjusted to the real needs of the installation and as a minimum to P 25 with P power in th h of the boiler The pump heating will have to allow to work in constant...

Page 85: ...LECTRICAL CONNECTION BX2 Gnd BX3 Gnd B3 Gnd B9 Gnd H1 Gnd H5 Gnd C RECOMMENDED HYDRAULIC ACCESSORY Order No Hydraulic kit for boiler only for EVO S 50 for EVO S 70 and S 95 for EVO S 115 for EVO S 135...

Page 86: ...e alarm output Relay output QX1 5890 Alarm output K10 Configure DHW pump Q3 Relay output QX2 5891 DHW ctrl elem Q3 Configuration menu Save the sensors Save sensors 6200 Yes switches back to no automat...

Page 87: ...Adjust the over value Flow setpoint boost 5020 16 C Maintenance optimisation A maintenance message may be generated that does not set the boiler to fault This maintenance message may be displayed afte...

Page 88: ...it 1 QAD 36 219487 The existing regulation controls all the circuits of the installation It determines the outlet set point temperature that the installation requires and sends it to the boilers eithe...

Page 89: ...d BX3 Gnd B3 Gnd B9 Gnd H1 Gnd H5 Gnd L N PWM GND Boiler pump if supplied by IDEAL 230 VAC 50 Hz power supply Alarm relay Cascade cylinder outlet sensor B10 0 to 10V analogue input Boiler pump if supp...

Page 90: ...AL No adjustments necessary Boiler pump supplied by the customer all or nothing control Relay output QX3 5892 Boiler pump Q1 Diagram VF10 page 3 7 Boiler No 2 and the following ones L2 N L3 N L3 L1 N...

Page 91: ...valence 10 V 100 C For a request via LPB Check that the secondary regulatory is defined on an LPB segment other than 0 reserved for the generators In all cases LPB network menu Configure the boiler as...

Page 92: ...pply function 6604 Automatically Clock mode 6640 Slave without remote setting Connect the bus between the boilers pay attention to the polarity Switch off then switch on the slave boiler s If the comm...

Page 93: ...7700 Relay output QX1 Boiler pump control if supplied by customer Relay test 7700 Relay output QX3 Reset the outputs Relay test 7700 No test Check the sensor values Cascade cylinder outlet sensor B10...

Page 94: ...ssioning set parameter 7044 to 12 months Operating hours of the burner parameter 7040 Number of starts parameter 7042 These last 2 parameters are dependent on the boiler s hydraulic installation We re...

Page 95: ...it 1 QAC 34 219479 Network sensor kit 1 QAD 36 219487 The master NAVISTEM B3000 controls the cascade of boilers on the basis of the outlet temperature measured by the sensor QAD 36 Each NAVISTEM B3000...

Page 96: ...l sensor B9 Alarm relay DHW pump Q3 B3 DHW sensor Cascade cylinder outlet sensor B10 Boiler pump if supplied by customer U BX22 M BX21 M H2 Regulated circuit output sensor B1 QX21 N QX22 N QX23 N L Mi...

Page 97: ...lay Boiler pump if supplied by customer U BX22 M BX21 M H2 Regulated circuit output sensor B1 2 QX21 N QX22 N QX23 N L Mixing valve heating circuit n 3 Y1 2 Y2 2 Heating circuit No 3 circulator Q2 2 U...

Page 98: ...figuration menu Start up heating circuit 1 Heating circuit 1 5710 On Start up heating circuit 2 Heating circuit 2 5715 On Configure the alarm output Relay output QX1 5890 Alarm output K10 Configure DH...

Page 99: ...k to no automatically On boiler n 2 or the following boilers slave Configuration menu Boiler pump supplied by IDEAL No adjustments necessary Boiler pump supplied by the customer all or nothing control...

Page 100: ...ting regime to permanent comfort Connect the bus between the boilers pay attention to the polarity Switch off then switch on the slave boiler s If the communication has been correctly established the...

Page 101: ...sensor Sensor temp BX21 module 2 7832 in C Configuration menu Check the hydraulic diagram Check no heat source 1 6212 14 Check no heat source 2 6213 0 Check no storage tank 6215 4 Check no heating ci...

Page 102: ...ing circuit 1 2 menu Adjust the reduced setting Reduced setpoint 712 1012 ECO function for automatic summer winter switch see NAVISTEM B3000 manual Summer winter heating limit 1030 1330 19 C Daily ECO...

Page 103: ...boiler to fault This maintenance message may be displayed after the following 3 counters have expired Time since last maintenance or commissioning set parameter 7044 to 12 months Operating hours of th...

Page 104: ...and 100 Pump speed min 2322 between 0 and 100 Pump speed max 2323 between 0 and 100 9 4 2 Controlling a Q2 Q6 or Q20 heating circuit pump D SPECIFIC START UP PROCEDURE Line No Value Configuration men...

Page 105: ...the DHW pump Q3 Function output Ux 6078 6089 Pompe ECS Q3 Signal direction Progress of the 0 10V signal in the signal increase direction for speed increase Signal logil output UX 6079 6090 Standard D...

Page 106: ...106 136 00RNO0333 B U0625869 EVO S Installation and Servicing...

Page 107: ...27 08 2018 107 136 EVO S Installation and Servicing 10 SPARE PARTS LIST figure 33 Trim shown on EVO S 50 U0568687 I II 001 002 003 004 005 006 002 007 009 008...

Page 108: ...or right side jacket AH78690 AH78699 AH78700 AH78710 003 Jacket fasteners x 4 AH76644 004 Adhesive seal for font side jacket long 3 5 m AH76649 005 Concentric adaptor AH78609 AH78610 006 Adaptor seals...

Page 109: ...27 08 2018 109 136 EVO S Installation and Servicing figure 34 Control panel U0568658 U0505839 U0505841 II 101 102 103 110 112 111 113 114 104 105 106 106 107 108 108 107 109 109 115...

Page 110: ...20 AH71898 108 Square fuse holder with fuse AH76129 109 Customer platform connectors AH76128 110 Complete display user interface AH78475 111 Display alone user interface with selector AH78477 112 Plas...

Page 111: ...ation and Servicing figure 35 Body and burner for EVO S 50 model U0568698 B III 201 202 203 204 205 206 203 207 208 209 203 210 211 213 212 214 215 216 217 218 203 205 219 220 233 231 232 221 222 223...

Page 112: ...nising electrode seal AH76463 214 Ignition electrode seal AH76462 215 Burner holder refractory insulation AH76471 216 Exchanger bottom refractory insulation AH76470 217 Exchanger AH76457 218 Customer...

Page 113: ...ervicing figure 36 Body and burner for EVO S 70 to 115 models U0568698 A IV 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 312 328 329 330...

Page 114: ...urner holder rail AH76473 AH76526 319 Ignition electrode seal AH72505 320 Ionising electrode seal AH72506 321 Burner rail seal AH76467 AH76468 322 Burner holder refractory insulation AH76472 323 Excha...

Page 115: ...ation and Servicing figure 37 Body and burner for EVO S 135 model U0591163 V 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 412 428 430 433...

Page 116: ...H76666 416 Seal burner holder braid AH72153 417 Burner holder safety thermostat AH76476 418 Complete burner holder rail AH76474 419 Ignition electrode seal AH72505 420 Ionising electrode seal AH72506...

Page 117: ...uage E English 22 Info C Temporarily 26 Operation lock C Off 27 Programming lock C Off 28 Direct adjustment C Storage with confirmation 29 Units E C bar 42 Assignment device 1 C CC 1 44 Operation HC2...

Page 118: ...rogram 5 600 Preselection E Mo Su 601 First period start time E 06 00 602 First period stop time E 22 00 603 Second period start time E 24 00 604 Second period stop time E 24 00 605 Second period star...

Page 119: ...ator type S 3 position 833 TOR Switching differential S 2 C 834 Actuator running time S 120 s 835 Mixing valve Xp S 32 C 836 Mixing valve Tn S 120 s 850 Floor curing function C Off 851 Floor curing se...

Page 120: ...xing valve Xp S 32 C 1136 Mixing valve Tn S 120 s 1150 Floor curing function C Off 1151 Floor curing setp manually C 25 C 1155 Floor curing setp current E 0 C 1156 Floor curing day current E 0 1161 Ex...

Page 121: ...5 Floor curing setp current E 0 C 1456 Floor curing day current E 0 1461 Excess heat draw S Always 1470 With buffer S No 1472 With prim contr system pump S No 1481 Starting speed S 100 1482 Pump speed...

Page 122: ...No Swimming pool 2055 Setpoint solar heating S 26 C 2056 Setpoint source heating S 22 C 2065 Charging priority solar S Priority 3 2080 With solar integration S Yes Boiler 2203 Release below outside t...

Page 123: ...diff off min DHW S 3 C 2462 Switching diff off max DHW S 6 C 2463 Settling time DHW S 20 min 2470 Delay heat req special op C 0 s 2503 Parameter S 6 s 2630 Auto deaeration procedure S Off 2655 ON time...

Page 124: ...controller 1 S None 5574 Sensor 2 controller 1 S None 5575 On time min dT contr 1 S 0 s 5577 Pump valve kick K21 S On 5580 Temp diff on dT contr 2 S 20 C 5581 Temp diff off dT contr 2 S 10 C 5582 On...

Page 125: ...C None 6037 Relay output QX22 module 3 C None 6038 Relay output QX23 module 3 C None 6040 Sensor input BX21 module 1 C None 6041 Sensor input BX22 module 1 C None 6042 Sensor input BX21 module 2 C Non...

Page 126: ...ent address S 0 6604 Bus power supply function S Automatically 6605 Bus power supply state S Automatically 6610 Display system messages S No 6611 Syst messages alarm relay S No 6620 Action changeover...

Page 127: ...diagnostic code 7 S 0 6866 Burner control phase 7 S 0 6870 History 8 S 00 00 6873 Error code 8 S 0 6875 SW diagnostic code 8 S 0 6876 Burner control phase 8 S 0 6880 History 9 S 00 00 6883 Error code...

Page 128: ...story 20 S 00 00 6993 Error code 20 S 0 6995 SW diagnostic code 20 S 0 6996 Burner control phase 20 S 0 Service special operation 7040 Burner hours interval S 1500 h 7041 Burn hrs since maintenance S...

Page 129: ...module 3 C Open 7854 Voltage signal H3 C 0 V 7855 Contact state H3 C Open 7860 Contact state H4 C Open 7862 Frequency H4 C 0 7865 Contact state H5 C Open 7872 Contact state H6 C Open 7874 Contact stat...

Page 130: ...15 C Missing 8130 Priority source 16 C 0 8131 State source 16 C Missing 8138 Cascade flow temp C 0 C 8139 Cascade flow temp setp C 0 C 8140 Cascade return temp C 0 C 8141 Cascade return temp setp C 0...

Page 131: ...h 8530 Hours run solar yield E 00 00 00 h 8531 Hours run collect overtemp E 00 00 00 h 8532 Hours run collector pump E 00 00 00 h 8560 Solid fuel boiler temp C 0 C 8570 Hours run solid fuel boiler E 0...

Page 132: ...C 8860 DHW flow C 0 l min 8875 Flow temp setp VK1 C 5 C 8885 Flow temp setp VK2 C 5 C 8895 Flow temp setp swimming pool C 5 C 8900 Swimming pool temp C 0 C 8901 Swimming pool setpoint C 24 C 8930 Prim...

Page 133: ...trol 9504 Required speed prepurging S S 50 S 70 S 95 S 115 S 135 3130 2450 2750 2590 3410 9512 Required speed ignition S S 50 S 70 S 95 S 115 S 135 3130 2300 2350 2480 3410 9524 Required speed LF S S...

Page 134: ...n QHE kWh Acoustic power LWA dB IDEAL EVO S 50 EVO S 70 219427 219428 56 70 A A 93 93 56 4 69 9 87 6 87 4 18 9 23 4 98 0 97 4 0 138 0 096 0 028 0 025 0 003 0 003 0 051 0 087 35 35 2 2 60 57 Data on pr...

Page 135: ...27 08 2018 135 136 EVO S Installation and Servicing...

Page 136: ...2 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal...

Reviews: