Installation and Servicing
On the RVS 63:
Line No. Value
• Inputs/outputs test
menu
Check the outputs
HC3 pump (Q2)
Relay test
(7700)
HC pump Q2
HC3 3-channel valve opening
Relay test
(7700)
HC mixing valve
open Y1
HC3 3-channel valve close
Relay test
(7700)
HC mixing valve
close Y2
HC4 pump (Q6)
Relay test
(7700)
Pompe CdeC Q6
HC4 3-channel valve opening
Relay test
(7700)
HC mixing valve
open Y5
HC4 3-channel valve close
Relay test
(7700)
HC mixing valve
close Y6
Reset the outputs
Relay test
(7700)
No test
Check the sensor values
Circuit 3 network flow sensor (B1)
Flow temp. B1
(7732)
en °C
Circuit 4 network flow sensor (B12)
Flow temp. B12
(7734)
en °C
Diagram: VF4
page 7 / 8
G. CONFIGURATION OPTIMISATION
On EVO S boiler and RVS 63 :
Heating circuit optimisation:
•
Heating circuit 1 / 2
menu
Adjust the reduced setting
Reduced setpoint
(712/1012)
- - -
ECO function for automatic
summer / winter switch (see
NAVISTEM B3000 manual)
Summer/winter heating limit
(1030/1330)
19 °C
Daily ECO function for automatic
comfort / reduced switch
according to the difference
between the set point and
the outdoor temperature (see
NAVISTEM B3000 manual).
24-hour heating limit
(1032/1332)
-3 °C