60 / 136
00RNO0333-B (U0625869)
EVO S -
Installation and Servicing
Diagram: VF3
page 7 / 7
Maintenance optimisation
A maintenance message may be generated that does not set the boiler to fault. This maintenance
message may be displayed after the following 3 counters have expired:
•
Time since last maintenance (or commissioning): set parameter 7044 to 12 months.
•
Operating hours of the burner (parameter 7040).
•
Number of starts (parameter 7042)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.
H. CONFIGURING THE ROOM SENSOR
Connecting the sensor to the heating circuit:
Line No. Value
•
User interface
menu of the
room sensor
Assign the heating circuit to the room sensor
Use
(40)
Ambience appliance
2
The room sensor is used to configure the heating circuit. It adjusts parameter 1012 (heating circuit 2).
Refer to the NAVISTEM B3000 manual for the other room sensor functions.